1070 072 449-102 (01.12) GB
Status Display5-2
Explanation:
Operational Mode: Normal operational status. Cyclic I/O data exchange
without error and warnings.
Remote Test: A special test program is processed (the JP1 soldering
jumper must be closed).
SYNC Mode: The outputs remain frozen until the next SYNC or UNSYNC
commands are received.
FREEZE Mode: The inputs remain frozen until the next FREEZE or
UNFREEZE commands are received.
SYNC/FREEZE Mode: Superimposition of SYNC and FREEZE mode.
CLEAR Mode: Upon receipt of a CLEAR command, the outputs are
unlatched. An UNCLEAR command from the master will reset this status.
The reading of the input data will be continued.
I/O diagnostic message: One or more I/O modules indicate an error.
LEAVE Master: The slave is at the bus, i.e. that it is synchronous to the
baud rate and waits for the parameterization and configuration by a
master. Reasons for this indication are:
Slave is not addressed by a master (wrong node address).
The address monitoring function for the master has become inactive.
Wrong ID number in the parameterization message.
Parameterization data length too large.
Offline: The slave cannot synchronize itself to the baud rate or it is not at
the bus.
Parameterization Error: The parameterization data sent by the master
does not correspond to that of the slave.
Configuration Error: The configuration data sent by the master does not
correspond to that of the slave.
Hardware test active: Carry out the hardware test in POWER_ON
status.
Peripheral bus Init: One or more peripheral bus modules are still in their
initialization phase and hold the RM2-DP12 module in POWER_ON
status.