1070 072 449-102 (01.12) GB
I/O Modules 6-3
6.5 Limits of Expansions
With regard to the expansion possibilities of the CL200 peripherals, the
following limit values exist for the modular DP station:
Please observe the limit value of the current! The I/O modules'
maximum current input from the peripheral bus supply (7.5 V) must
not exceed 1.2 A!
For inputs, a maximum of 244 bytes is supported.
For outputs, a maximum of 244 bytes is supported.
The sum of all possible in- and outputs is 384 bytes.
A maximum of 38 I/O modules.