1070 072 449-102 (01.12) GB
Technical Data9-2
Mechanical stress (shock and vibration
resistance):
Vibrations: Sinusoidal oscillations in all 3 axes as per
IEC 1131-2
Frequency 10 - 57 Hz
with 0.0375 mm constant amplitude
with 0.075 mm occasional amplitude
Frequency 57 - 150 Hz
with 0.5 g constant amplitude,
with 1.0 g occasional amplitude
Shock: Impact resistance on all 3 axes as per IEC 1131-2,
semi-sinusoidal, duration: 11 ms with 15 g.
Interference radiation:
Harmful radiation None
Radio interference suppression of housing Class A, test conditions as per EN 50081-2:
Frequency 30 - 230 mHz,
limit value 30 dB (mV/m) in 30 m
frequency 230 - 1000 mHz
limit value 37 dB (mV/m) in 30 m
EMI resistance:
High-frequency electromagnetic fields as per
IEC 1131-2
Test field strength: 10 V/m
Frequency range: 27 to 500 MHz
Sweep rate: 0.0015 dec./s
Electrostatic discharges on accessible housing
parts as per EN 50082-2. ESD resistance 4 for
humidity rating RH-2.
Air discharge: 16 kV
Contact discharge: 6.5 kV
Conducted interferences:
24V voltage supply Rapid burst pulses, symmetrical:
4 kV as per IEC 801-4
Dampened sine wave 1 MHz, symmetrical as per
IEC 255-4: not relevant
Serial data line (DP bus)
Rapid burst pulses, symmetrical:
4 kV as per IEC 801-4
Dampened sine wave 1 MHz, symmetrical as per
IEC 255-4: not relevant