Fan Motor Options | 27Revised 08/14
8 733 914 818 (2014/08)SV Heat Pump Series
Table 7: Constant Airflow Motor Performance Table
Model
Fan
Speed
Rated
Airflow
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20
SV-015
A - Low
450 450 450 450 450 450 450 440 440 430 - -
A - Normal
500 500 500 500 500 500 500 500 480 470 460 - -
A - Hi
580 580 580 580 580 580 580 570 560 550 - -
SV-018
B - Low
550 540 540 540 540 540 540 530 520 500 - -
B - Normal
650 650 650 650 650 650 650 640 630 610 590 - -
B - Hi
750 750 750 750 750 750 740 730 710 690 - -
SV-024
C - Low
720 720 720 720 720 720 720 700 650 560 - -
C - Normal
850 850 850 850 850 850 850 850 850 800 700 - -
C - Hi
960 960 960 960 960 960 960 960 880 790 - -
SV-030
D - Low
810 810 810 810 810 810 810 810 810 810 - -
D - Normal
950 950 950 950 950 950 950 950 950 950 950 - -
D - Hi
1090 1090 1090 1090 1090 1090 1090 1090 1090 1090 - -
SV-036
A - Low
1020 1020 1020 1020 1020 1020 1020 1020 1020 1020 - -
A - Normal
1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 - -
A - Hi
1380 1380 1380 1380 1380 1380 1380 1380 1380 1380 - -
SV-041
A - Low
1020 1020 1020 1020 1020 1020 1020 1020 1020 1020 - -
A - Normal
1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 - -
A - Hi
1380 1380 1380 1380 1380 1380 1380 1380 1380 1380 - -
SV-042
B - Low
1190 1190 1190 1190 1190 1190 1190 1190 1190 1190 - -
B - Normal
1400 1400 1400 1400 1400 1400 1400 1400 1400 1400 1400 - -
B - Hi
1630 1630 1630 1630 1630 1630 1630 1630 1630 1630 - -
SV-048
A - Low
1360 1360 1360 1360 1360 1360 1360 1360 1360 1360 - -
A - Normal
1600 1600 1600 1600 1600 1600 1600 1600 1600 1600 1600 - -
A - Hi
1840 1840 1840 1840 1840 1840 1840 1840 1840 1840 - -
SV-060
A - Low
1700 1700 1700 1700 1700 1700 1700 1700 1700 1700 1700 -
A - Normal
2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 -
A - Hi
2220 2220 2220 2220 2220 2220 2220 2220 2220 2220 2220 -
SV-070
B - Low
1870 1870 1870 1870 1870 1870 1870 1870 1870 1870 1870 -
B - Normal
2200 2200 2200 2200 2200 2200 2200 2200 2200 2200 2200 2200 -
B - Hi
2330 2330 2330 2330 2330 2330 2330 2330 2330 2330 2330 -
Note: Air flow is 70% of tabulated values during fan only operation. Air flow is 80% of tabulated value
during passive dehumidification mode when enabled.