INSTALLATION
6 720 644 842b (2010/12)
23
7.4 REDIRECTING THE FLUE DISCHARGE
Fig. 41 Plume direction conditions
The plume deflector can be adjusted to redirect the flue discharge.
NOTE: FLUE DISCHARGE
B The Plume terminal outlet position must follow those stated in figure 27. When redirecting the flue
discharge the outlet must be at least 1500mm from and angle at least 45° away from any opening in the
direction of the discharge, as shown. This is to prevent combustion products from entering the building.
1
2
3
45°
V
6720644842-28.1Wo
4
1 Opening in the building i.e. air brick, window.
2 Direction of flue products, must be more than
45° from the wall or structure
3Plume terminal
4 At least 1500mm from any opening in the
building
Table 16 Key to figure 41