Service and Spares
Greenstar Danesmoor Utility
ErP+
and Utility System
ErP+
- 6 720 821 720 (2018/04) 47
Fig. 85 Baffle detail
Fig. 86 Baffle positioning
7.10 Oil supply system and tank
▶ The oil pipeline, filters, fire valve and tank should be inspected and
maintained in accordance with OFTEC regulations.
7.11 Clean the boiler - Manifold access
Refer to figures 87.
▶ Release screws [1] to remove the flue manifold access cover [2] and
clear any debris.
▶ Check the flue system and clean if necessary.
▶ Remove the baffle retainer [3] and baffles [4] from the secondary
heat exchanger.
▶ Check and clean the secondary heat exchanger surfaces.
▶ Check the condensate route [5] is clear.
▶ The condensate trap [7] should be removed and cleaned.
▶ Release the pipe locking tab [8] and disconnect the flexible pipe [9]
from the top of the trap and move the flexible pipe up away from the
trap.
▶ Release the trap locking tab [10] and move the trap up and back to
remove from its mountings.
▶ Clean the trap by flushing with water.
▶ Check the O ring seals and replace if necessary, grease the seals with
a solvent free grease.
▶ Refit the trap making sure that the locking tabs are locked in place.
▶ Pour 500 ml of water into drain [5] to refill the condensate trap and
check that the condensate discharge pipe is discharging.
▶ Clean the secondary heat exchanger baffles [4] if necessary and refit
correctly.
▶ Refit the baffle retainer [3].
▶ Check and clean the flue damper, ensure that it is correctly fitted
▶ Check the seal on the manifold access cover [6] and replace if
necessary.
▶ Refit the flue manifold access cover [2] and secure with screws [1].
Fig. 87 Secondary heat exchanger and condensate trap detail
7.12 Re-commissioning the burner
Fig. 88 18/25 and 25/32 Burner O-ring seal shown
1. Align burner combustion head into burner collar.
Do not use wire brushes or cleaning agents to clean the
stainless steel secondary heat exchanger components.
6720808218-92.1Wo
12/18kW
Baffle
18/25 & 25/32kW
Baffle
6720808218-78.1Wo
C
D
WARNING: Flue gas leakage
The seal between the burner and the mounting flange
must form a gas tight seal to prevent leakage of
potentially dangerous gas from the combustion
chamber.
▶ Unless the burner is level when pushing the burner
into the flange the O-ring may not seat properly
allowing flue gas to escape!
▶ Always check that the O-ring seal (Fig 88item A) is in
good condition before fitting the burner.
Replace the O-ring seal if defective.
6720821683-19.1Wo
9
7
8
10
6
2
3
4
5
1
6720821683-25.1Wo
A