Bosch Worcester TDS 10 - Key to Illustrations in Appendix; Unvented DHW Cylinders

Bosch Worcester TDS 10
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6
Product details
6 720 612 217 (05.03)
Solar panel high-temperature cut-
out (fixed setting)
Above a temperature of 130 °C at
the solar panel temperature sensor
the solar heating system pump
switches off.
The display shows the hot panel/
evaporation symbol and the sym-
bol stops moving (Fig. 5, page 16).
The solar heating system pump
does not switch on again until the
solar panel temperature has
dropped below 127 °C and the stor-
age tank temperature sensor
calls for heat.
At temperatures above 140 °C the
convector fluid evaporates in the
solar panel.
Indication of excessive tempera-
ture difference (fixed setting)
If the temperature difference -
is greater than 80 K, this can be a
sign that there is air in the system or
that the solar heating system pump
is defective.
Display error message: SYS.
1.5 Key to illustrations in
Appendix
Key to Figures 1 to 10 on pages 16
to 18:
Solar heating system pump
Solar panel temperature sensor
(PTC)
Storage tank temperature
sensor (PTC)
No function
1 Top fixing hole
2 Bottom fixing holes
230 V AC Power supply connection
3 Spare fuse, 4 A MT, 250 V
4 Fuse 4 A MT, 250 V
5 Cable exits to rear
6 Cable exits to underneath
7 Inner programmer cover
(protects electronics)
S Mode selector switch
Si Fuse, 4 A MT, 250 V
TDS 10 Solar heating system
programmer
1.6 Unvented DHW Cylinders
When connecting the Greenskie's
Solar Heating System to an un-vented
hot water storage cylinder, it is recom-
mended that the electrical supply to
the solar control system is taken via the
thermal cut-out device on the cylinder.