Assembly
15
Condens 5000W – 6720813952 (2019/02)
Without connection set
Connect flexible hose to the siphon.
5.12 Connecting the condensate drain
NOTICE:
Boiler damage.
Make sure there is an open connection between the wall mounted gas
condensing boiler and condensate discharge pipe.
Use a waste water pipe made of plastic material with a diameter of at
least Ø 32 mm to remove the condensate.
Install a siphon in the waste water pipe.
Connect horizontal pipe sections with a gradient to the waste water
pipe.
The maximum length of the horizontal pipe section in this case is 5 m.
Fill siphon in the waste water pipe.
5.13 Expansion vessel connection
Determine the size and supply pressure of the expansion vessel based on
EN 12828.
If the option to connect the expansion vessel to the connection set is
used with a cascade installation on the reverse side (TR), a right-angled
coupling is required in the front row of the wall mounted gas condensing
boilers.
Remove the cap from the connection point [1].
Connect the connection pipe of the expansion vessel to the
connection point.
Fig. 21 Expansion vessel connection
5.14 Mounting the back panel insulation
Hook back panel of the connection set into the wall mounted gas
condensing boiler.
Fig. 22 Mounting the back panel (insulation)
5.15 Connection of air supply and flue system
The flue pipe documentation is included in the scope of delivery of the
wall mounted gas condensing boiler.
Read these instructions carefully before the installation.
Connect the air supply and flue gas pipe according to the instructions
for this flue gas routing accessory.
5.15.1 Flue terminal positions
NOTICE:
Install a fire proof board if installing on combustible surfaces.
The location of the flue terminal must comply with the clearances
shown on this page. If you are unsure about clearances not indicated
here, in general refer to AS/NZS5601 or your local authority. In
Western Australia refer to SECWA rules and regulations.
All measurements are the minimum clearances required.
Terminals must be positioned to avoid combustion products entering
the building.
The fixing method must be sufficient to hold the weight of the boiler.