Product Information
9
Condens 5000W – 6720813952 (2019/02)
2.13 Specifications
Table 2 Specifications
The information in brackets corresponds to the information on the data plate.
Type 70 Type 100
General Information Unit
Rated output G20 (50/30 °C) [P
n
cond] kW 14.3 – 69.5 20.8 – 99.5
Rated output G20 (80/60 °C) [P
n
] kW 13.0 – 62.6 19.0 – 94.5
Rated input G20 [Q
n
(Hi)] kW 13.3 – 64.3 19.3 – 96.5
Nominal input NG/G20 MJ/h 257 386
Efficiency G20 (37/30 °C) partial load 30% in accordance with EN 15502 % 107.8 107.9
Efficiency G20 (80/60 °C) full load % 97.4 97.0
Standby loss in accordance with EN 15502 % 14 9
Seasonal efficiency, heating curve (75/60 °C) % 106.8 106.7
Seasonal efficiency, heating curve (40/30 °C) % 109.4 109.5
Pump run-on time min 5 5
Residual head of fan (p
max
) Pa 130 220
IP classification [IP rating] IP X4D (B
23
, B
33
: X0D)
Appliance class in accordance with EN 15502 B
23
, B
33
, C
13(x)
, C
33(x)
, C
43(x)
, C
53(x)
, C
83(x)
, C
93(x)
Temperature classification in accordance with EN 14471 T120
Appliance fuse 230 V, 5AF
Mains voltage, frequency [U] 230 V, 50 Hz
Electrical power consumption (without a pump connection set),
standby / partial load / full load
W 6 / 18 / 82 6 / 25 / 155
Permissible ambient temperature °C 0 - 40
Maximum flow temperature [T
max
]°C90
Maximum permissible water pressure of the wall mounted gas condensing
boiler [PMS]
bar 4
Maximum condensate accumulation rate l/h 7.6 11.0
Connections
Flue gas connection/concentric air supply mm 100/150
Heating flow/return pipe (wall mounted gas condensing boiler) inch G1½
Gas connection (wall mounted gas condensing boiler) inch R1
Condensate drain (flexible drain hose) mm 24
Emission levels in accordance with EN 13384
CO
2
content with natural gas G20, partial load/full load % 8.9 / 9.3 8.9 / 9.3
CO output G20 at full load ppm 57 100
NO
x
emission G20 at full load in accordance with EN 15502 (average) mg/kWh 27 48
NO
x
class 5
Flue gas mass flow rate at max./min. rated output g/s 29.8 43.8
Flue gas temperature at 80/60 °C, partial load/full load °C 57 / 62 57 / 68
Flue gas temperature at 50/30 °C, partial load/full load °C 34 / 39 34 / 53
Differential pressure gas/air (with partial load) Pa - 5
Dimensions and weight
Height x width x depth mm 980 x 520 x 465
Height x width x depth incl. connection set mm 1300 x 520 x 465
Weight kg 70
Connection set
Heating flow pipe inch G1½
Heating return pipe, male thread with flat gasket inch G1½
Gas line inch G 1
Electrical power consumption WILO Stratos PARA 25/1-8, min./max. W 8 / 140