7. Connection
Fault current in safety switch by customers
We recommend by customers to install a universal sensitive fault current safety switch.
At frequency controlled drive machines you have to install a universal sensitive fault
current safety switch.
P 240 /P 300 USA Operating load max. current Fuse
kW A A
___________________________________________________________________________
400 V, 50 Hz
steam heated 4.5 15.1 20
electrical heated 13.7 27.8 35
steam heated with Slimsorba 5.2 17.3 20
electrical heated with Slimsorba 20.1 38.4 50
230 V, 50 Hz
steam heated 4.3 19.4 25
electrical heated 13.6 41.6 50
steam heated with Slimsorba 5.0 22.9 35
electrical heated with Slimsorba 20.2 59.8 80
230 V, 60 Hz
steam heated 4.3 20.2 25
electrical heated 13.4 41.8 50
steam heated with Slimsorba 4.9 23.7 35
electrical heated with Slimsorba 20.1 59.0 80
200 V, 50 Hz
steam heated 4.9 23.5 35
electrical heated 14.1 49.0 63
steam heated with Slimsorba 5.6 27.2 35
electrical heated with Slimsorba 19.8 66.5 80