EasyManua.ls Logo

BPC PowerPro HP310 - The Power Configuration of UPS

Default Icon
41 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6
PowerPro HP300 Series User Manual
NOTE: The battery circuit breaker must be turn to “1” position when a voltage comes to the main.
If not in a second main failure the critical load will be without Voltage.
C. On maintenance by-pass: UPS shutdown but the load connected to the unprotected mains via
the maintenance by-pass supply line.
D. Parallel operation : At least 2 UPS’s is installed to system for increasing security and redundancy
, they operates together and interactive.
1.2.2 The Power Configuration of UPS
The power switch location of the T-300P series UPS’s are shown in the figures 1.1-2-3-4 In the figure 1.2
external (split) by-pass block diagram is given. Optionally the static and mechanic by-pass line can be
connect to a different 3 phase AC source ( other UPS etc.),and the rectifier input is connected to generator or
mains voltage. If there is no other power supply static and mechanic by-pass line input (S2) and the rectifier
input connections will be connect to each other. (See figure 1.1)
During the normal operation except the maintenance by-pass switch, all the Switches will be at “1-On”
position (closed).
3 phase
load
output
Inverter
Rectifier
Static By-Pass
Static Transfer Switch
Maintenance Bypass
Mechanic transfer switch
3 Phase
Line
Input
Battery group
S3
S2
S1
S5
S4
3 Phase
By-Pass
Supply
Input
Figure 1.2 UPS Split (external) By-Pass Block Diagram

Table of Contents

Related product manuals