Classic Circular 36"/54" Washfountain with Foot Control
Installation Instructions WF2605, WF2608 Terrazzo — WF2705, WF2708 Stainless Steel
Bradley Corporation 215-603 Rev. M; EN 06-915B
54/6/2007
Rough-In Notes:
1. All pipes and fittings not furnished by Bradley are shown in broken lines.
2. Supply lines for one to two washfountains should be 1"; for three washfountains 1-1/4"; for more
than three washfountains, pipe sizes should be increased proportionately.
3. Overhead supplies must be reduced to 1/2" copper tube to pass through support tube.
4. Check valve inlets are 1/2" NPT.
5. Dimensions shown in parentheses are millimeters.
4"
(102)
4"
(102)
Cold
Cold
1-1/4"
(32)
NOTE: UPC and IPC restrict the vertical
distance from the fixture outlet to the trap
weir to not more than 24". Check state and
local codes for variances.
7-5/8"
(194)
7-5/8"
(194)
Type A
Off-line vent with
supplies from below
Type B
Centrally rising vent with
supplies from above
1" NPT supplies from above
must reduce to 1/2 nom. copper
tube on these centers to
pass thru washfountain
1" NPT supplies through
floor: stub up 2-1/2" (64)
above floor
2" NPT drain:
stub up 3" (76)
above floor
36" (914) bowl
36" (914) bowl
54" (1372) bowl
54" (1372) bowl
2-1/2"
(64)
7/8"
(22.2)
7/8"
(22.2)
Hot
Hot
1-1/2" NPT vent to ceiling
2" NPT drain:
stub up 3" (76)
above floor
TOP VIEW
TOP VIEW
Rough-In Specifications