13 Installer Guide
15 AC Power Interrupt Warning [note 6]–Whenenabled,thethermostatwilldisplayanoutagewarning
whenACpowertothethermostatislost.
16 Short Cycle Protection [note 7]–Selectsthenumberofminutesthecoolingcompressorwillbelocked
outafterturningoff.Thisshortcycleprotectionisalsoactiveintheheatmodeifaheatpumpsystemwas
selectedinOption6.
17 Residual Cooling Fan Delay [note 7]–Selectsadelayforthesystemfanafterthecoolingcompressor
hasturnedoff.Thisdelaywillhelpremovetheremainingcoolairoutoftheductworkprovidingadditional
efciency.
18 Adaptive Recovery Mode (early recovery) [note 8]–EnablesordisablestheARM
TM
(adaptiverecovery
mode)feature.DuringARM,roomtemperatureisrecoveredbyturningontheheatingorcoolingbeforethe
endofthesetbackperiod.Thesetpointtemperatureischangedtothatoftheupcomingprogramtemperature.
19 Indoor Remote Sensor Control [note 9]–IfaBraeburn
®
indoorremotesensorisconnectedduring
installation,thethermostatwillautomaticallydetectthesensor.Whenanindoorsensorisdetected,youmay
selectbetweenthermostatonly(ISENS),remotesensoronly(ESENS)orcombiningthethermostatandthe
remotesensor(ASENS).NOTE: This option does not apply to a Braeburn outdoor sensor. When an outdoor
sensor is connected the thermostat automatically recognizes it and no further configuration is necessary.
20 Lockout Security Level–Selectsthelevelofkeypadlockoutwhenthethermostatislocked.Level2locks
theentirethermostat(includingthefrontresetbutton).Level1lockseverythingexcepttheSpeedBar
®
allowingforupanddowntemperatureadjustment.NOTE: The lock code is set in the User Settings mode
(see User Manual).
21 Auto Changeover Dead Band [note 10]–Whenautochangeovermodeisenabledinoption5and
selected,thesystemautomaticallyswitchesbetweenheatingandcoolingwhentheroomtemperature
meetsthenormalcriteriaforeitheraheatingorcoolingcall.Thereisaforcedseparation(deadband)
betweentheheatingandcoolingsetpointssothatthesystemsdonotworkagainsteachother.This
optionselectstheamountofthisdeadbandindegreeswiththedefaultbeing3°F.
22 Compressor Balance Point [notes 4, 11]–Locksouttheuseofthecompressorheatstagewhenthe
outsideairtemperatureislessthantheselectedsettingof15°Fto50°F(-9°Cto10°C)
23 Auxiliary Heat Balance Point [notes 4, 11]–Locksouttheuseoftheauxiliaryheatstagewhenthe
outsideairtemperatureexceedstheselectedsettingof70°Fto40°F(21°Cto4°C).NOTE: This balance
point overrides the fossil fuel compressor lockout in option 13. If this option is set to gas and the outdoor
temperature is over the auxiliary balance point, the compressor will remain on during a call for auxiliary heat.
24 Heat Set Point Upper Limit–Selectstheheatingsetpointupperadjustmentlimit.
25 Cool Set Point Lower Limit [note 7]–Selectsthecoolingsetpointloweradjustmentlimit.