EasyManuals Logo

Bray 6A series User Manual

Bray 6A series
42 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #30 background imageLoading...
Page #30 background image
All information herein is proprietary and confidential and may not be copied or reproduced without the expressed written consent of BRAY INTERNATIONAL, Inc.
The technical data herein is for general information only. Product suitability should be based solely upon customer’s detailed knowledge and experience with their
application.
Series 6A Installation, Operation & Maintenance – Technical Data
6A O & M : 30
TECHNICAL DATA
1. Basic Units
3-/4-wire device (terminals 2/4 and
6/8) (6DR52.. and 6DR53..)
Power supply U
H
18 ... 35 V DC 18 ... 30 V DC
Current consumption I
H
(U
H
- 7.5 V)/2,4 kΩ [mA]
Internal capacitance C
i
22 nF 22 nF (at "nL")
Internal inductance L
i
0.12 mH 0.12 mH (at "nL")
For connection to circuits with the
following peak values
intrinsically safe
U
i
= 30 V DC
I
i
= 100 mA
P
i
= 1 W
at "nA" and "tD":
U
n
= 30 V DC
I
n
= 100 mA
at "nL":
U
i
= 30 V DC
I
i
= 100 mA
Current input I
W
Rated signal range 0/4 ... 20 mA
Load voltage at 20 mA 0.2 V (corresponds to 10 Ω) 1 V (corresponds to 50 Ω)
Internal capacitance Ci 22 nF 22 nF (at "nL")
Internal inductance Li 0.12 mH 0.12 mH (at "nL")
For connection to circuits with the
following peak values
intrinsically safe
U
i
= 30 V DC
I
i
= 100 mA
P
i
= 1 W
at "nA" and "tD":
U
n
= 30 V DC
I
n
= 100 mA
at "nL":
U
i
= 30 V DC
I
i
= 100 mA
Electrical isolation between U
H
and I
W
between U
H
and I
W
(2 intrinsically safe cir-
cuits)
between U
H
and I
W
Test voltage 840 V DC, (1 s)
Connections
Electrical Screw terminals 2.5
AWG28-12
Cable gland M20x1.5 or
½-14 NPT
Screw terminals 2.5
AWG28-12
Ex d certified cable gland
M20x1.5, ½-14 NPT or
M25x1.5
Screw terminals 2.5 AWG28-12
Cable gland M20x1.5 or ½-14 NPT
Pneumatic
Female thread G1/4 EN ISO 228-1 or
¼ -18 NPT
External position sensor (potentiome-
ter or NCS; as option) with the follow-
ing peak values
U
o
5 V
I
o
(static) 75 mA
I
s
(short-time) 160 mA
P
o
120 mW
Maximum permissible external
capacitance C
o
1 μF
Maximum permissible external
inductance L
o
1 mH
SIPART PS2 Basic device
without Ex protection
Basic device
with Ex d protection
(flameproof enclosure)
Basic device
with Ex ia/ib protection
Basic device
with Ex n/
dust protection
Technical specifications

Other manuals for Bray 6A series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bray 6A series and is the answer not in the manual?

Bray 6A series Specifications

General IconGeneral
BrandBray
Model6A series
CategoryValve Positioners
LanguageEnglish

Related product manuals