In general, the following is recommended for all persons working with or on the BlueEye™ Ex-D:
• Training / education for work in hazardous areas.
• The ability to correctly estimate dangers and risks when working with the BlueEye™ Ex-D.
• Training / education by Bright Sensors SA for work with gas measuring devices.
• Education / instruction in all national standards and directives to be complied with for the work to be
carried out on the BlueEye™ Ex-D.
Operating personnel:
The operating personnel use and operate the device in the scope of the intended use.
Maintenance personnel:
Work on the device must only be carried out by qualified personnel who can carry out the respective tasks
on the basis of their technical training, experience and familiarity with the applicable standards and
requirements. These qualified personnel are familiar with the applicable statutory regulations for accident
prevention and can independently recognize and avoid potential dangers.
Maintenance and cleaning:
Maintenance and cleaning must only be performed by appropriately qualified technicians.
The device can be damaged if it is not cleaned as specified in the operating manual. Only clean the device
as specified in the operating manual. Components can be damaged if you do not use suitable tools.
- Only clean the device with a slightly damp cloth!
The BlueEye™ Ex-D enclosure is epoxy coated. Under certain extreme conditions it may generate an ignition-
capable level of electrostatic charges.
- DO ensure that the equipment is NOT installed in a location where it may be subjected to
external conditions (such as high-pressure steam) which might cause a build-up of
electrostatic charges on non-conducting surfaces.
1.4 Certification for hazardous areas
Hazardous area classifications:
• Zone 0: An area classified as Zone 0 will have ignitable concentrations of flammable gases, vapours
or liquids either continuously present or present for long periods of time under normal operating
conditions.
• Zone 1: An area classified as Zone 1 is likely to have ignitable concentrations of flammable gases,
vapours or liquids present under normal operating conditions. Flameproof (Exd) detectors are suitable
for use in Zone 1.
• Zone 2: An area classified as Zone 2 is not likely to have ignitable concentrations of flammable gases,
vapours or liquids present under normal operating conditions. Flameproof (Exd) detectors are suitable
for use in Zone 2.
• Areas that may contain flammable dusts are categorized as Zone, 20, Zone 21 and Zone 22.