EasyManua.ls Logo

BRINKS BHS-4000A - 3.2 Wiring System Zones; 3.2.1 Wiring the burglary zones; 3.2.2 Wiring the fire zone; 3.3.2 Wiring multiple keypads

BRINKS BHS-4000A
24 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
BHS-4000A
Installation
and
Programming
Instructions
3.2
W
ire
the
zones
3.2.1
W
iring
the
burglary
zones
Burglary
zones
circuits
can
have
a
normally-open,
normally-
closed,
or
an
end-of-line
(EOL)
configuration.
For
UL
applications,
however,
an
end-of-line
configuration
is
required.
When
configuring
an
EOL
circuit,
use
a
minimum
22
AWG
wire
and
a
maximum
wire
length
less
than
1000
feet.
Wire
the
zone’s
detection
device(s)
according
to
the
manufacturer’s
instructions.
Connect
the
sensor
between
the
appropriate
Z
terminal
on
the
panel
and
the
adjacent
common
terminal.
3.2.2
W
iring
the
fire
zone
The
BHS-4000A
panel
is
designed
for
four-wire
smoke/heat
detectors
only.
Fire
zones
always
require
the
EOL
configuration.
Wire
the
smoke/heat
detector
as
outlined
below:
1.
Connect
the
positive
power
loop
wire
to
the
FIRE
terminal.
2.
Connect
the
negative
power
loop
wire
to
one
of
the
common
terminals.
3.
Connect
the
detection
loop
to
the
zone
and
common
terminals
on
the
panel.
Make
sure
the
zone
is
configured
as
a
fire
zone.
4.
When
using
the
System
Sensor
Model
2112ATL
Smoke
Detector,
connect
the
Sync
terminal
to
the
Siren
output.
System
Sensor
Model
2112ATL
Smoke
Detector
A
//
0
>.
!
/
'
111
11-
L__.
I
i
rC
.
Other
listed
4-wire
Smoke
Detector
using
a
listed
EOL
Relay
module
Wiring
the
smoke
detector
5.
C
onnect
the
smoke
detector
using
14
-
22
AWG
wire.
The
maximum
wiring
distance
is
not
to
exceed
500
feet.
3.3
W
ire
the
keypad
3.3.1
Connect
the
keypad
wires
to
the
terminals
Connect
the
keypad
wires
to
the
terminals,
as
follows:
Keypad
terminal
Panel
terminal
v+
AUX
V-
-
(Common)
CLK
CLK
DATA
DATA
Note:
Connect
the
keypad
using
a
minimum
22
AWG
wire
and
a
maximum
wire
length
of
650
feet.
3.3.2
W
iring
multiple
keypads
The
BHS-4000A
can
support
up
to
16
keypads,
but
they
can
have
ID
numbers
that
range
from
1
-128.
These
keypads
can
be
connected
in
daisy-chain
(parallel),
individually
home-run,
or
wired
using
a
combination
of
these
two
methods.
A
combination
of
LED
and
icon
keypads
can
be
used
in
the
same
installation.
3.4
W
ire
the
digital
communicator
The
digital
communicator
is
integrated
into
the
BHS-4000A
control
panel.
To
connect
the
panel
to
the
house
phone,
do
the
following:
1.
Locate
the
8-conductor
cable,
attached
to
the
right-hand
side
of
the
BHS-4000A’s
main
PCB.
2.
Insert
the
cable’s
plug
into
an
RJ31X
or
an
RJ38X
jack.
3.
Wire
the
RJ31X
jack
as
shown:
.To
panel
Incoming
Telephone
Une
Wire
the
RJ31X
jack
Note
The
colors
of
house
phone
wires
vary.
If
the
wire
colors
do
not
match
the
diagram
above,
connect
the
yellow
wire
to
the
wire
that
was
connected
to
terminal
4,
and
connect
the
black
wire
to
the
wire
that
was
connected
to
terminal
5.
3.5
Wire
the
ZEM
3.5.1
Connect
the
wires
to
the
terminals
Wire
the
ZEM,
following
the
instructions
below:
1.
Disconnect
the
system’s
AC
and
DC
power.
2.
Wire
the
ZEM
according
to
the
table
and
illustration.
ZEM
terminal
Panel
terminal
V+
AUX
V-
-
(Common)
CLK
CLK
DATA
DATA
GND
EARTH
Ground
(optional)
*
3.
W
i
r
e
the
zone
inputs
in
the
same
manner
used
to
connect
devices
to
the
panel’s
eight
on-board
inputs.
*
If
the
ZEM
is
mounted
more
than
10
feet
from
the
control
panel,
a
separate
earth
ground
connection
is
recommended.
Refer
to
Section
3.11.2
for
additional
information
on
connecting
to
earth
ground.
3.5.2
D
aisy
chaining
To
simplify
the
system’s
wiring,
devices
can
be
daisy-chained
together.
Use
each
device’s
V+,
V-,
CLK,
and
Data
terminals
for
making
daisy
chain
connections.
Daisy
chaining
is
not
recommended
and
extreme
care
should
be
taken
when
using
this
wiring
method.
If
daisy
chaining
is
used,
a
broken
wire
or
loose
connection
in
one
device
affects
all
additional
devices
in
the
chain.

Related product manuals