Brivo ACS-SDC-E Installation Manual
Follow safety precautions
WARNING: Fire Code
Never connect a keypad/reader or lock to doors without rst consulting the applicable re code. You must consult
with, and get approval from, local re ocials before installing locks or devices on any doors that may be re exits.
Use of egress push buttons may not be legal. Single action exits may be required. Always obtain proper permits and
approvals in writing before installing equipment
WARNING: Fail Secure Mode
Do not install the system in the fail secure mode unless permitted by the local authority having jurisdiction. Doing
so may cause interference with the operation of panic hardware.
WARNING: Heat and Noise
Do not install the control panel in an area that does not comply with the listed temperatures below. Doing so can
cause damage to components within the control panel.
The ACS-SDC-E control panel is UL tested to between -35°C (-31°F) and 66°C (150°F) and EN -40°C (-40°F) to 70°C
(158°F) and 85% humidity.
Do not install the control panel near or on the same circuit with devices that produce large amounts of electrical
noise. This includes grinders, electric motors and blowers, electrical switch-gear and other electrically noisy equip-
ment. Electrical noise can interfere with panel operation. If it is not possible to install the panel away from such
sources of noise, it is advisable to isolate it by using a high-quality UPS (Uninterruptible Power Supply) between the
AC Mains and the transformer.
· Unit is primarily for indoor use. It can be used outdoors if contained in a protected water tight
enclosure.
· Power wiring attached to the ACS-SDC-E unit should be 18 AWG or larger.
· Category 5 cabling is the minimum performance category recommended.
· Do not connect to a receptacle controlled by a switch.
· Compliance with IEEE 802.3 (at or af) specications was not veried as part of UL294/B.
· If powered by 12V DC, the power supply must be a UL294 listed or UL 603 listed power supply.
Battery capacity for loss of primary power at least zero (0) hours.