Site Manual
Alarm 2000 Iss 5
45
17. Primary power source
Dedicated circuit
18. Is the appropriate circuit breaker marked ‘FIRE ALARM SYSTEM’?
Yes No
19. Power supply capacity …………………………………………………...
20. Standby batteries - type and capacity …………………………………
21. Is the power supply and battery capacity the correct size to meet the system standby and
alarm time requirements?
Yes No
22. Has the ‘fire’ mode been tested for correct operation?
Yes No
23. Does the ‘system OFF’ indicator flash with the key switch in the off position?
Yes No
24. Has the operator’s handbook been supplied?
Yes No
25. Have ‘as-installed’ drawings been supplied?
Yes No
NOTE: ANY DEFECTS WITH SYSTEM INSTALLATION MUST BE RECTIFIED PRIOR
TO THE COMMISSIONING AND HANDOVER.
I/We hereby certify that the installation has been thoroughly tested;
from each actuating device; and
the system functions as required; and
where the system is remotely monitored, that a test transmission of the alarm
signal to the monitoring centre has been satisfactorily carried out; and
the system complies to the requirements of the Building Code of Australia; and
is as represented in the ‘as-installed’ drawings and this installer’s statement.
Date: ………………………
Name: ……………………………………
Signature: ……………………………….
Installation company: ……………………………………………………….
Address: ……………………………………………………………………...
Phone: …………………………………