BROOKS AUSTRALIA RFP6 Installer ISSUE 4
32
Step 3. Turn the Panel key switch to "OFF'; wait approximately 10 seconds, then
turn the system back on.
6.2 Faults
A fault is present when the sounder in the Control Panel sounds continuously (or
beeps about every 30 seconds with the Sounder Silence switch activated) and no red
alarm LED is illuminated.
6.2.1 Line Fault
If a zone fault (amber) LED is illuminated and the sounder is sounding continuously,
then an Open Circuit or Short Circuit has occurred. If a Short Circuit has occurred then
the fuse on the zone will be blown. If an Open Circuit has occurred the fuse will be
intact. The field wiring should be disconnected and metered to locate the source of the
fault.
6.2.2 Low Battery
If the Control Panel sounder emits a short beep about every 30 seconds and no red or
amber LED is illuminated and the Sounder Silence switch is not activated, a low
battery condition is indicated. This may be caused by the 240 volt Mains being off for
at least 72 hours. Mains power should be restored as a matter of urgency. If the Mains
has not been off, call the service technician responsible immediately.
FOR FURTHER ASSISTANCE PLEASE DO NOT HESITATE TO CONTACT YOUR
LOCAL DISTRIBUTOR OR BROOKS FIRE AND WARNING SYSTEMS