BROOKS AUSTRALIA RFP6 Installer ISSUE 4
15
2.2 Specifications
No. of zones : 6
No. of Smoke/Heat Alarms: 72 max (12 per zone)
Power Supply : Input 240V AC
Output 12.3 -13.8 VDC, Typical 13.70 VDC
Standby Supply : 12V/6.5AH sealed lead acid battery
Battery low setting : 12.3 VDC
Keyswitch Operation : “ON” System ON - Charger ON
“OFF” System OFF - Charger ON
“FIRE” activates all smoke/heat alarms
System Monitoring : Wiring loop in and loop out to Smoke/Heat
Alarms monitored by active End of Line Device
Defect Mode : Initiated by an abnormal system condition:
* Mains Fail
* Ancillary output (common alarm) Isolated
* Short circuit line fault
* Open circuit line fault
* System switched off
Defect Output (Fault) : 1 set changeover dry contact
Alarm Outputs : 12V DC 1 Amp maximum
1 set changeover dry contact
Panic Input : N/O dry contact - activates all S/H Alarms
Note: Not monitored
Sounder Silence Switch : Acknowledges panel sounder
Alters tone from continuous to chirp (for
battery low and line fault)
Ancillary Isolate Switch : Isolate common alarm outputs
Initiate Defect Mode
Alarm Locate Switch : Silences all Smoke/Heat Alarms except those
initiating the alarm . Interlocked to fire mode
to prevent accidental operation
Visual Indications : Individual zone alarm - Red
Individual zone fault - Amber
Ancillary isolate - Amber
Locator activated - Amber
Sounder silence - Amber
Power ON - Green