130
PERFORMANCE DATA (cont)
POWER EXHAUST POWER REQUIREMENTS
LEGEND
MOCP — Maximum Overcurrent Protection
0
500
1000
1500
2000
2500
0.05" 0.15" 0.25"
Static Pressure (in. wg)
Flow in cubic feet per m inute (cfm)
3-6 Ton
7 1/2 - 12 1/2 Ton
0
5
10
15
20
25
30
0.1" 0.2" 0.3" 0.4" 0.5"
Static Pressure (in. wg)
Flow in cubic feet per minute (cfm)
3-6 Ton
7 1/2 - 12 1/2 Ton
Vertical EconoMi$er IV and EconoMi$er2
Performance Data (581B036-150)
0
1000
2000
3000
4000
5000
0 0.1 0.2 0.3 0.4 0.5
3-6 Ton
7.5-12.5 Ton
STATIC PRESSURE (in. wg)
FLOW (cfm)
VERTICAL POWER EXHAUST PERFORMANCE
Horizontal EconoMi$er IV and EconoMi$er2
Performance Data (581B036-150)
0
500
1000
1500
2000
2500
0 0.1 0.2 0.3 0.4 0.5
STATIC PRESSURE (in. wg)
FLOW (cfm)
HORIZONTAL POWER EXHAUST PERFORMANCE
0
500
1000
1500
2000
2500
0.05
0.15
0.25
STATIC PRESSURE (in. wg)
FLOW IN CUBIC FEET PER MINUTE (cfm)
3-6 Ton
7 1/2 - 12 1/2 Ton
0
5
10
15
20
25
30
0.13 0.20 0.22 0.25 0.30 0.35 0.40 0.45 0.50
3-6 Ton
7 1/2-12 1/2 Ton
STATIC PRESSURE (in. wg)
FLOW IN CUBIC FEET PER MINUTE (cfm)
BAROMETRIC RELIEF FLOW CAPACITY
OUTDOOR AIR DAMPER LEAKAGE
BAROMETRIC RELIEF CAPACITY
OUTDOOR AIR DAMPER LEAKAGE
a48-6308
a48-6202
a48-6203
a48-6225
a48-6224
a48-6309
POWER EXHAUST
SIZE
AMPS AT 230 V
(2 FANS RUNNING)
MOCP
230 VAC 460 VAC 575 VAC
3 to 6 Ton
1.40 amps
at 60 Hz
15.0
amps
15.0
amps
15.0
amps
7
1
/
2
to 12
1
/
2
Ton
3.04 amps
at 60 Hz
581B036-150