SG-619AHB-01: Service Manual
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
25
DIAGNOSIS AND SOLUTION (CONT)
Overload current protection diagnosis and solution (F0)
Malfunction Decision Conditions
An abnormal current rise is detected by checking the specified current detection circuit.
Possible Causes:
Power supply problems
System blockage
PCB faulty
Wiring mistake
Compressor malfunction
Troubleshooting
Check the power supply.
Check the connection and the wires.
Stop the unit.
No
Yes
No
Correct the connections or
replace the wires.
Yes
Replace the outdoor unit.
Yes
Check the reactor
No
Replace outdoor main PCB.
Check for system blockage.
Yes
No Clear the blockage.
Check the compressor
resistance values.
Yes
No Replace the compressor.