EasyManua.ls Logo

Bryant 986TC - VENTING SYSTEM INSTALLATION; Venting System Planning and Materials; Canada Venting Requirements

Bryant 986TC
76 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
986TC: Installation, Start-up, Operating, Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
30
7. Configure thermostat for single-stage compressor operation. Refer to thermostat instructions.
8. Configure thermostat for two-stage compressor operation. Refer to thermostat instructions.
9. Configure thermostat for HYBRIDHEATr dual fuel operation. Refer to thermostat instructions.
10. NO connection should be made to the furnace HUM terminal when using a thermostat with a 24 volt humidifier output.
11. Optional connection - If wire is connected to W2 on furnace control board, either dip switch SW1-2 or SW1-LHT on furnace control should be set
in ON position to allow thermostat to control furnace staging.
12. Optional connection - If wire is connected to Y2 on furnace control board, ACRDJ jumper on furnace control should be removed to allow
thermostat to control outdoor unit staging.
13. Furnace must control its own staging operation via furnace control algorithm. This is factory default.
14. The RVS Sensing terminal “L” should not be connected. This is used internally to sense defrost operation.
15. If thermostat has internal control of heat pump balance point, DO NOT SELECT the “FURNACE INTERFACE” or “BALANCE POINT” option
on the two-speed heat pump control board. Refer to thermostat instructions
16. Configure Dehumidify function to remove 24 VAC from Dehum terminal on a demand to dehumidify.
17. Thermostat signals may vary. Consult thermostat installation instructions for more information.
VENTING
NOTE: Planning for the venting system should be done in conjunction
with planning for the ductwork, drainage, and furnace accessories, such
as air cleaners and humidifiers. Begin assembling the venting system
AFTER the furnace is set in place in the required orientation.
Venting for this furnace shall follow all Local codes for Category IV
venting systems. This furnace is CSA approved for venting with
PVC/ABS DWV venting systems. This furnace is also CSA approved
for venting with M&G DuraVentRPolyProR or Centrotherm InnoFlueR
polypropylene venting systems using single wall straight and flex, and
required fittings (elbows, reducers, increasers, connectors, adapters)
only.
NOTE: THESE INSTRUCTIONS DO NOT CONTAIN DETAILED
INSTALLATION INSTRUCTIONS FOR POLYPROPYLENE
VENTING SYSTEMS. Refer to the polypropylene venting system
manufacturer’s installation instructions for the polypropylene venting
system installation.
NOTE: When using polypropylene venting systems, all venting
materials used, including the vent terminations, must be from the same
manufacturer.
Special Venting Requirements for Installations in
Canada
Installation in Canada must conform to the requirements of CSA B149
code. Vent systems must be composed of pipe, fittings, cements, and
primers listed to ULC S636. The special vent fittings, accessory
concentric vent termination kits and accessory external drain trap
available from the furnace manufacturer have been certified to ULC
S636 for use with those Royal Pipe and IPEX PVC vent components
which have been certified to this standard. In Canada, the primer and
cement must be of the same manufacturer as the vent system – GVS-65
Primer (Purple) for Royal Pipe or IPEX System 636, PVC/CPVC
Primer, Purple Violet for Flue Gas Venting and GVS-65 PVC Solvent
Cement for Royal Pipe or IPEX System 636
(1)
t, PVC Cement for Flue
Gas Venting, rated Class IIA, 65 deg C. must be used with this venting
system - do not mix primers and cements from one manufacturer with a
vent system from a different manufacturer. Follow the manufacturer’s
instructions in the use of primer and cement and never use primer or
cement beyond its expiration date.
The safe operation, as defined by ULC S636, of the vent system is based
on following these installation instructions, the vent system
manufacturer’s installation instructions, and proper use of primer and
cement. All fire stop and roof flashing used with this system must be UL
listed material. Acceptability under Canadian standard CAN/CSA B149
is dependent upon full compliance with all installation instructions.
Under this standard, it is recommended that the vent system be checked
once a year by qualified service personnel.
The authority having jurisdiction (gas inspection authority, municipal
building department, fire department, etc.) should be consulted before
installation to determine the need to obtain a permit.
*IPEX System 636™ is a trademark of IPEX Inc.
Consignes spéciales pour l’installation de
ventilation au Canada
L’installation faite au Canada doit se conformer aux exigences du code
CSA B149. Ce systême de ventillation doit se composer de tuyaux,
raccords, ciments et apprêts conformes au ULC S636. La tuyauterie de
ventilation des gaz, ses accessoires, le terminal concentrique mural ainsi
que l’ensemble du drain de condensation extérieur fourni par le fabricant
de cette fournaise ont été certifiés ULCS 636 pour l’application des
composantes Royal Pipe, IPEX PVC qui sont certifiées à ce standard.
Au Canada, l’apprêt et le ciment doivent être du même fabricant que le
système dévacuation. L’apprêt GVS-65 (Purple) et le ciment-solvant
GVS-65 doivent être utilisé avec les Royal Pipe. Système IPEX 636,
apprêt PVC/CPVC, Purple pour évacuation des gaz de combustion et
système IPEX 636(1)t, ciment PVC pour évacuation des gaz de
combustion, coté classe IIA, 65 deg C. doivent être utilisés avec le
système d’évacuation IPEX 636 – Ne pas combiner l ’apprêt et le ciment
d’un manufacturier avec un système d’évacuation d’un manufacturier
différent.
Bien suivre les indications du manufacturier lors de l’utilisation de
l’apprêt et du ciment et ne pas utiliser ceux-ci si la date d’expiration est
atteinte.
L’opération sécuritaire, tel que définit par ULC S636, du système de
ventilation est basé sur les instructions d’installation suivantes, ainsi que
l’usage approprié de l’apprêt et ciment. Tout arrët feu et solin de toit
utilisés avec ce système doivent être des matériaux listés UL.
L’acceptation du standard Canadien CAN/CSA B149 est directement
relié à l’installation conforme aux instructions ci- haut mentionnées. Le
standard Canadien recommande l’ inspection par un personel qualifié et
ce, une fois par année.
Les autoritées ayant juridiction (inspecteurs de gas, inspecteurs en
bâtiments, département des incendies, etc) devraient être consultées
avant l’installation afin de déterminer si un permis est requis.

Related product manuals