33
ADVANCED
SETUP
(CONT)
MAT T CAL 0.0
°
F ±2.5°F
SUPPLY AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of calibration temperature
sensor.
OAS T CAL 0.0
°
F ±2.5°F
OUTSIDE AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of calibration temperature
sensor.
OA H CAL 0% RH ±10% RH
OUTSIDE AIR HUMIDITY CALIBRATION
Allows for operator to adjust for an out of calibration humidity sensor.
RA T CAL 0.0
°
F ±2.5°F
RETURN AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of calibration temperature
sensor.
RA H CAL 0% RH ±10% RH
RETURN AIR HUMIDITY CALIBRATION
Allows for operator to adjust for an out of calibration humidity sensor.
DA T CAL 0.0
°
F ±2.5°F
DISCHARGE AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of calibration temperature
sensor.
2SP FAN DELAY 5 Minutes
0 to 20 minutes
in 1 minute
increments
TIME DELAY ON SECOND STAGE ECONOMIZING
When in economizing mode this is the delay for the high speed fan to
try to satisfy the call for second stage cooling before the first stage
mechanical cooling is enabled.
CHECKOUT
DAMPER MINIMUM
POSITION
N/A N/A
The checkout for the damper minimum position is based on the
system. See Table 12.
DAMPER OPEN N/A N/A
Position damper to the full open position.
Exhaust fan contacts enable during the DAMPER OPEN test. Make
sure to pause in the mode to allow exhaust contacts to energize due
to the delay in the system.
DAMPER CLOSE N/A N/A Positions damper to the fully closed position
CONNECT Y1–O N/A N/A Closes the Y1-O relay (Y1-O)
CONNECT Y2–O N/A N/A Closes the Y2-O relay (Y2-O)
CONNECT AUX1-O N/A N/A
Energizes the AUX output. If Aux setting is:
• NONE — not action taken
• ERV — 24 Vac out. Turns on or signals an ERV that the conditions
are not good for economizing but are for ERV operation.
• SYS — 24 Vac out. Issues a system alarm
CONNECT EXH1 N/A N/A Closes the power exhaust fan 2 relay (EXH1)
ALARMS
Alarms display only when they are active. The menu title “ALARMS(#)” includes the number of active alarms in parenthesis ( ).
When using SYLK bus sensors, “SYLK” will appear on the screen, and when using 20k OA temperature sensors, “SENS T” will
appear on the screen
MA T SENS ERR N/A N/A
SUPPLY AIR TEMPERATURE SENSOR ERROR
Mixed air sensor has failed or become disconnected - check wiring
then replace sensor if the alarm continues.
CO2 SENS ERR N/A N/A
CO
2
SENSOR ERROR
CO
2
sensor has failed, gone out of range or become disconnected -
check wiring then replace sensor if the alarm continues.
OA SYLK T ERR N/A N/A OUTSIDE AIR S-BUS SENSOR ERROR
Outdoor air enthalpy sensor has failed or become disconnected -
check wiring then replace sensor if the alarm continues.
OA SYLK H ERR N/A N/A
RA SYLK T ERR N/A N/A RETURN AIR S-BUS SENSOR ERROR
Return air enthalpy sensor has failed or become disconnected - check
wiring then replace sensor if the alarm continues.
RA SYLK H ERR N/A N/A
DA SYLK T ERR N/A N/A
DISCHARGE AIR S-BUS SENSOR ERROR
Discharge air sensor has failed or become disconnected - check
wiring then replace sensor if the alarm continues.
OA SENS T ERR N/A N/A
OUTSIDE AIR TEMPERATURE SENSOR ERROR
Outdoor air temperature sensor has failed or become disconnected -
check wiring then replace if the alarm continues.
ACT ERROR N/A N/A
ACTUATOR ERROR
Actuator has failed or become disconnected - check for stall, over
voltage, under voltage and actuator count. Replace actuator if damper
is movable and supply voltage is between 21.6 V and 26.4 V. Check
actuator count on STATUS menu.
FREEZE ALARM N/A N/A
Check if outdoor temperature is below the LOW Temp Lockout on
setpoint menu. Check if Mixed air temperature on STATUS menu is
below the Lo Setpoint on Advanced menu. When conditions are back
in normal range then the alarm will go away.
Table 11 — Menu Structure (cont)
MENU PARAMETER
PARAMETER
DEFAULT
VALUE
PARAMETER
RANGE AND
INCREMENT
NOTES

Other manuals for Bryant Legacy Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bryant Legacy Series and is the answer not in the manual?

Bryant Legacy Series Specifications

General IconGeneral
Cooling Capacity1.5 to 5 tons
SeriesLegacy Series
Compressor TypeSingle-Stage
RefrigerantR-410A
Warranty10-year parts limited warranty upon timely registration

Related product manuals