4.2 Installation Position
The installation position shall meet the following requirements:
✓ There are no inflammable and explosive materials nearby.
✓ The ambient temperature shall be within the range of - 10 ℃ to 50 ℃.
✓ It must be installed on the horizontal floor or wall that can support its
weight.
✓ The distance from the air outlet of the inverter shall be more than 0.5m.
✓ It shall be installed under the eaves indoors (such as garage or basement)
or outdoors to avoid direct sunlight and water immersion.
Suggestion:
The installation area shall be dry, ventilated and free of corrosive gas;
The area has the least dust and dirt;
The product should be installed in a place where children and animals
cannot reach;
The ambient temperature range is 10 ℃~35 ℃.
If the ambient temperature exceeds the working range, the PB2 will stop
working and enter the protection state.
Frequent exposure to harsh temperatures may reduce the performance and
life of the PB2.
4.3 Physical Requirements
PB2-5.1 supports floor and wall mounted installation. When it is installed on the
floor, it must also be fixed on the adjacent wall. In these two installation methods,
the wall must be able to support the weight of the PB2-5.1 body and its
accessories. It is recommended that the minimum strength of the wall shall not
be less than 17Mpa (concrete) or 10Mpa (masonry).