EasyManua.ls Logo

Buderus AM10 - Communication Fault (5 H); Sensor Fault and Emergency Operation

Buderus AM10
40 pages
Go to English
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
User Manual
AM10 - We reserve the right to make any changes due to technical modifications!12
2
Target point of heating characteristics
The "Mode" key was used to select the " "
symbol. This concerns the target point of the
heating characteristic corresponding with an
outdoor temperature of 14 °F. The value will
flash and can be changed using the plus "
+"
and minus "" keys.
Adjustment range: 68 - 194 °F.
Factory setting: 167 °F.
Base point of heating characteristics
The "Mode" key was used to select the " "
symbol. This concerns the base point of the
heating characteristic corresponding with an
outdoor temperature of 68 °F. The value will
flash and can be changed using the plus "
+"
and minus "
" keys.
Adjustment range: 68 - 194 °F.
Factory setting: 86 °F.
Warm weather shut down (WWSD)
The "Mode" key was used to select the
WWSD temperature " ". This concerns
the maximum outdoor temperature at which
the heating is still operational.
The value will flash and can be changed using
the plus "
+" and minus "" keys.
Adjustment range: 32 - 86 °F.
Factory setting: 70 °F.
Fig. 13 Display of third menu item
8163
°F
Fig. 14 Display of fourth menu item
100
°F
Fig. 15 Display of fifth menu item
868
°F

Other manuals for Buderus AM10