EasyManua.ls Logo

Buderus EM10 - EM10 Communication and Signals; Communication bus setup; Malfunction signal generation; External control signal (0-10 V)

Buderus EM10
48 pages
Go to English
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Module EM10 English
Changes due to technical improvements reserved
Module EM10 • 01/2008 13
Communication bus
Connect the EMS connection (fig. 2, pos. 6) of the EM10
with a 2-core cable to the RC- (or -) connection on the
boiler (possibly parallel to the thermostat).
Caution: This connection is polarity sensitive. The total
length of the EMS bus cable may be no more than 100 m.
Malfunction signal
The malfunction signal is given when:
a locking malfunction occurs in the boiler,
the system pressure is too low or
the communication with the boiler has been interrupted
for at least 5 minutes. See wiring diagram on page 47.
The EM10 generates two malfunction signals:
a) The AS 24 V connection (fig. 2, pos. 4), this is a
potential-free switching contact for low voltage signals of
up to 24 V. This malfunction signal can for example, be
evaluated by a building management system.
b) The AS 230 V connection (fig. 2, pos. 3), this can for
example operate a horn or warning light. In case of a
malfunction, there will be 230 VAC on this connection.
External control signal 0-10 V
The EM10 can be used as an interface between the boiler
and, for example, a building management system.
With the 0-10 V DC signal (fig. 2, pos. 5), the flow tempera-
ture or the power of the boiler can be controlled (fig. 3).
a) Flow temperature-based control
The EM10 transfers the 0-10 V signal to a flow
temperature-setpoint. This is a linear ratio, see table 1.
fig. 2 Connections
pos. 1: 230 V mains supply
pos. 2: 230 V connection for a 2nd module
pos. 3: Alarm output 230 V
pos. 4: Alarm output 24 V
pos. 5: Control signal 0-10 V
pos. 6: Input EMS bus
pos. 7: Output EMS bus
AS (230V)
N
L
Netz moduleNetz module
AS 24V U EMS EMS
123 1231212
1 2 3 4567
AS 24 V no malfunction malfunction
1 and 2 interrupted closed
2 and 3 closed interrupted
fig. 3 0 – 10 V diagram
Flow temperature [° C]
External control voltage (V)
Input
voltage
Flow temperature
Setpoint (boiler)
Status
Boiler
0 V - 0.5 V 0 off
0.6 V ± 15° C on
5.0 V ± 50° C on
10.0 V ± 90° C on/maximum
table 1 Flow temperature-based control

Related product manuals