For the contractor
Please read these instruc-
tions carefully
Gas valve replacement
instructions
Condensing gas boiler
Logamax plus
Required Input Rates
Logamax plus GB162-80 kW Logamx plus GB162-100 kW
290,000 btu/hr 333,000 btu/hr
This instruction is for replacing the gas valve for the GB162
model boilers with Natural Gas.
WARNING!
Replacement of a gas valve must be done by a qualified service
agency in accordance with the manufacturer‘s instructions and all
applicable codes and requirements of the authority having
jurisdiction.
The information in these instructions must be followed to minimize
the risk of fire or explosion or to prevent property damage,
personal injury or death. The qualified service agency is
responsible for the proper installation of this kit.
The installation is not proper and complete until the operation of
the converted boiler is checked as specified in the manufacturer‘s
instructions supplied with the gas valve.
CAUTION!
The gas supply shall be shut off prior to disconnecting the
electrical power, before proceeding with the conversion.
Notice! Save these instructions for later use.
GB162-80 kW
GB162-100 kW
6 720 615 152 (11/2011) US/CA