Defines the intended use of the conversion set for G334X heaters from natural gas to propane.
Explains additional symbols used for identifying dangers and user instructions within the manual.
Warns about explosion risk from flammable gases and requires licensed personnel for gas line work.
Details mandatory safety precautions and initial steps for converting the boiler from natural gas to propane.
Instructions for removing and installing new main gas orifices and adjusting the gas valve.
Procedures for disconnecting pilot burner gas line, ignition cable, and gas supply line.
Guidance on installing new main gas orifices and checking sizes based on boiler model.
Instructions for handling the pilot burner, reassembling the gas burner, and connecting various lines.
Details on filling out and attaching the conversion label to the boiler jacket.
Steps for performing a leak test using soap solution and measuring gas supply and manifold pressures.
Crucial safety warnings and procedures to follow if gas odor is detected or if the unit is submerged.
Steps to prepare the boiler for operation, including leak test confirmation and opening the main gas valve.
Procedure for starting the heating system when controlled by the factory-installed aquastat.
Instructions for starting the heating system with the optional Logamatic 2107 control.
General procedures to follow for startup, including observing the igniter through the sight glass.
Steps for igniting the pilot and main burners, checking for leaks, and ensuring proper flame.
Procedures for checking and adjusting gas supply and manifold pressures according to specified values.
Guidelines for adjusting the pilot flame size and ensuring it envelops the flame guard properly.
Procedures for observing the main burner flame, testing the ignition safety switch, and verifying gas valve operation.
Steps for turning off the gas valve, closing the shut-off valve, and re-checking screw plugs for leaks.
Verifying the function of the maximum aquastat to ensure it switches off the boiler at the set temperature.
Setting the Logamatic 2107 control to automatic mode after completing the conversion and startup.