Specifications
Logano G615 - Subject to technical modifications
12
Logano G615
Boiler
capacity
Unit 570 660 740 820 920 1020 1110 1200
Number of
boiler
sections
– 9 10 11 12 13 14 15 16
Nominal
output
Btu/hr
(kW)
1,743,604
1,944,921
(511 – 570)
1,948,333
2,252,014
(571 – 660)
2,255,426
2,524,984
(661 – 740)
2,528,397
2,797,956
(741 – 820)
2,801,368
3,139,170
(821 – 920)
3,142,582
3,480,385
(921 – 1020)
3,483,797
3,787,477
(1021
1110)
3,790,889
4,094,570
(1111
1200)
Thermal
output
Btu/hr
(kW)
1,865,077
2,102,562
(546.6
616.2)
2,083,795
2,434,563
(610.7
713.5)
2,412,384
2,729,713
(707.0
800.0)
2,704,122
3,024,864
(792.5
886.5)
2,996,202
3,393,716
(878.1
994.6)
3,360,960
3,760,180
(985.0
1102.0)
3,726,059
4,094,570
(1092.0
1200.0)
4,053,624
4,425,548
(1188.0
1297.0)
Overall boiler
length (L
G
)
inches
(mm)
75 53/64"
(1926)
82 33/64"
(2096)
89 7/32"
(2266)
95 29/32"
(2436)
102 19/32"
(2606)
109 19/64"
(2776)
115 63/64"
(2946)
122 43/64"
(3116)
Boiler block
length (L
K
)
inches
(mm)
71 1/64"
(1804)
77 23/32"
(1974)
84 13/32"
(2144)
91 7/64"
(2314)
97 51/64"
(2484)
104 31/64"
(2654)
111 3/16"
(2824)
117 7/8"
(2994)
Single boiler
section size
(B × H × T)
inches
(mm)
43 9/64" × 64 9/16" × 6 45/64"
(1096 × 1640 × 170)
Boiler block
transport
size
(B × H × L)
inches
(mm)
43 9/64" × 64 9/16" × L
K
(1096 × 1640 × L
K
)
Combustion
chamber
length (L
F
)
inches
(mm)
60 1/32"
(1525)
66 47/64"
(1695)
73 27/64"
(1865)
80 1/8"
(2035)
86 13/16"
(2205)
93 1/2"
(2375)
100 13/64"
(2545)
106 7/8"
(2715)
Combustion
chamber
diameter
inches
(mm)
26 49/64"
(680)
Burner door
thickness
inches
(mm)
5 4 5/64"
(145)
Weight, net
1)
lbs.
(kg)
5.523
(2505)
6.056
(2747)
6.592
(2990)
7.125
(3232)
7.661
(3475)
8.179
(3710)
8.715
(3953)
9.143
(4147)
Boiler water
content
gal
(l)
148.25
(561)
164
(621)
180
(681)
195.75
(741)
211.5
(801)
227.5
(861)
243.25
(921)
259.25
(981)
Gas capacity
gal
(l)
243.5
(922)
271.25
(1027)
299
(1132)
326.75
(1237)
354.5
(1342)
382.25
(1447)
410
(1552)
437.75284
(1657)
Flue gas
temperature
partial load
60 %
°F
C)
284
(140)
Flue gas
temperature
full load
°F
C)
338 – 356
(170 – 180)
Flue gas
mass flow
rate, oil,
partial load
60 %
°F
C)
32.277
(0.1537)
32.32
(0.1778)
32.359
(0.1995)
32.397
(0.2207)
32.446
(0.2479)
32.495
(0.275)
32.539
(0.2992)
32.582
(0.3234)
Tab. 4 Technical data and dimensions