6 720 804 895 – 2012/10 EN-US For heating engineers
Please read carefully before use
Conversion instructions
from natural gas to propane
R o o m a i r - i n d e p e n d e n t
special ga s - f ire d b oiler
Logano GA124
This conversion kit and the instructions are for conversion of the special gas-
fired boilers of the GA124 model from natural gas to propane.
Requirements
GA124 -17
70 MBtu/hr
GA124 -23
94 MBtu/hr
GA124 -30
123 MBtu/hr
WARNING!
This conversion kit must only be
installed by qualified heating contractor
as specified by the manufacturer’s
instructions and the applicable rules and
regulations of the local authorities. If
these instructions are not followed
exactly, a fire, explosion or release of
carbon monoxide may occur with
serious property damage or loss of life
and serious injury. The heating
contractor is liable for correct conversion
of the heating system with this
conversion kit.
CAUTION!
Before converting the heating system to
a different type of gas the gas line must
first be shut off and then the power to the
heating system must be disconnected.
Note: Please keep these instructions for future reference.

Other manuals for Buderus Logano GA124

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Buderus Logano GA124 and is the answer not in the manual?

Buderus Logano GA124 Specifications

General IconGeneral
BrandBuderus
ModelLogano GA124
CategoryBoiler
LanguageEnglish

Related product manuals