Page #40 background imageLoading...
Page #40 background image
40
We reserve the right to make any changes due to technical modifications!
Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Maintenance12
Removal of inducer.
1. Remove both screws (Fig. 34, Item. 1) on top rear
jacket cover (Fig. 34, Item. 2).
2. Remove top rear jacket cover (Fig. 34, Item. 2).
3. Remove the screws from the fan blower box and
remove the cover plate from the fan blower box.
4. Pull off the electrical connections.
5. Remove the screws from the flue collector.
6. Remove the screws (Fig. 35, Item. 3) that secure
the sheet metal blower base.
7. Check blower wheel for dirt and clean when
necessary.
8. Clean the boiler heat exchanger when necessary,
see 4.: “Cleaning the boiler“, page 41.
Fig. 34 Removal of the Top rear jacket cover
1
1
2
Fig. 35 Removal of the inductor
Item. 1: Fan blower box cover plate
Item. 2: Screws
Item. 3: Screws
Item. 4: Sheet metal blower base
1
2
3
4

Other manuals for Buderus Logano GA244