EasyManuals Logo

Burnham 8B Series User Manual

Burnham 8B Series
100 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #67 background imageLoading...
Page #67 background image
67
Table 12: Input Rate
b. Increase input rate if less than 98% of rating plate
input. Increase manifold gas pressure no more
than 0.3 inch w.c. If measured input rate is still
less than 98% of rated input:
i. Remove Main Burners per procedure in
Section IX: Service.
ii. Remove gas orifices. Drill one (1) drill size
larger (drill size is stamped on orifice, or
see Key No. 4E).
iii. Reinstall gas orifices and main burners.
Measure input rate.
6. Recheck Main Burner Flame.
7. Return other gas-fired appliances to previous
conditions of use.
N. Adjust gas input rate to boiler. LP/Propane.
1. Set thermostat to highest setting.
2. Adjust tank regulator for gas valve inlet pressure of
13.5 inches w.c. or less.
3. Gas valve has step opening regulator which initially
opens to 1.4 or 2.5 inch w.c. and steps to full
pressure after approximately 30 seconds. Check
manifold pressure after step has occurred. Adjust
gas valve pressure regulator as necessary for 10.0
inches w.c. (turn adjustment screw
counterclockwise to decrease manifold pressure, or
clockwise to increase manifold pressure). If 10.0
inches w.c. can not be attained, check gas valve
inlet pressure. If less than 11.0 inches w.c., contact
gas supplier for assistance.
O. Clean Heating System
Oil, grease, and other foreign materials which
accumulate in new hot water boilers and a new or
reworked system should be boiled out, and then
thoroughly flushed. A qualified water treatment
chemical specialist should be consulted for
recommendations regarding appropriate chemical
compounds and concentrations which are compatible
with local environmental regulations.
P. Check Damper Operation - If boiler is equipped with
vent damper, vent damper must be in open position
when boiler main burners are operating. Start boiler,
refer to instructions on damper to determine if damper
is in full open position.
Q. Install Front Removable Panel.
1. Engage top flange (longer of 2 flanges) behind
Upper Front Panel.
2. Swing lower portion of door toward boiler.
3. Lower door to engage bottom flange behind Lower
Front Tie Bar.
sdnoceS
enOrof
noituloveR
laiDreteMsaGfoeziS
flaH-enO
.tF.uC
enO
.tF.uC
owT
.tF.uC
eviF
.tF.uC
0306021042006
2365311522365
4335601212925
6305001002005
837459981474
045409081054
243468271034
441428461014
649387751193
847357051573
056327441063
255396831643
453376331333
652346921123
851326421013
060306021003
269285611092
469265211182
669245901372
868235601562
076215301752
275205001052
47428479342
67427459732
87326429132
08225409522
R. Combustion Chamber Burn-Off
1. The mineral wool combustion chamber panels
contain a cornstarch based binder that must be
burned out at installation to prevent odors during
subsequent boiler operation.
2. Ventilate the boiler room, set the high limit to its
maximum setting, set the thermostat to call for
heat.
3. Allow the boiler to fire for at least an hour or until
the odor from the cornstarch has dissipated.
4. Return the high limit and thermostat to their
desired settings.
S. Review User's Information Manual and system
operation with owner or operator.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Burnham 8B Series and is the answer not in the manual?

Burnham 8B Series Specifications

General IconGeneral
BrandBurnham
Model8B Series
CategoryBoiler
LanguageEnglish

Related product manuals