Alpine: Technical Information
Alpine Ratings & Specications
Model AFUE%
Input
(MBH)
min-max
DOE
Heating
Capacity
(MBH)
Net AHRI
(MBH)
Vent Size
(Inches)
Approx.
Shipping
Weight.
(lbs.)
*80-210MODELSAREAVAILABLEFORWALL(“W”suffix)ORFLOOR(“F”suffix)MOUNTING
ALP080B* 95 16-80 72 63 3 137
ALP105B* 95 21-105 96 83 3 155
ALP150B* 95 30-150 136 118 3 182
ALP210B* 95 42-210 194 169 3 206
FLOORMOUNTEDMODELS
ALP285B 95 57-285 262 228 4 256
ALP399 94
1
80-399 377
2
328
3
4 304
Standard Equipment
• Directventappliance
• Slide-outcontrolpanel
• Slide-outlinevoltageterminalstrip
• Sage2.1ControlSystem
–LCDtouchscreendisplay
–Self-guidedcontrolmenus
–100+helpscreens
–Built-inselfdiagnostics
–(3)separatecirculatoroutputs
–Built-insequencer,stagesupto(8)boilers
–4-20MVinputsforexternalcontrol
–Outdoorresetincludingoutsidesensor
–DHWpriority
–Warmweathershutdown
• Variablespeedcombustionblower
• Negativepressuregasvalve
• Stainlesssteelheatexchanger
• Polypropylenecondensatetrapw/overflowprotection
• Supply,return,andautoresethighlimitwatersensors
• Fluegastemperaturesensoranddifferentialpressureswitch
• Allconnectionsonleftsideofboiler
• CPVCtoPVCventkit
–Includes30”CPVC,90°elbow,2-ventterminals,screens,
andcombinationcement&primer
• Fiveyearparts&laborwarranty–sizesupto285MBH,
residentialonly,product registration required
A
S
M
E
Alpine
16-11/16”
L
Low Voltage
Knockouts (24V)
Line Voltage
Knockouts (115V)
One handle on
ALP80 & 105,
Two handles on
all other models
G
(Return
tapping)
F
(Gas valve inlet)
H
(Supply tapping)
3/4” FPT
relief/drain
tapping
J
(Condensate
trap drain)
M
N
O
P
D
C
E
B
Q
Optional Wall
Mount Bracket
7-3/16
*Factoryprovidedsocketendcompressionpipejoiningclampfor3/4”schedule40PVCpipe
Alpine CPVC to PVC Vent & Intake Sizes
Model
Intake
Size
Vent
Size
Max Length
Intake/Vent
ALP080B 3” 3” 135’/135’
ALP105B 3” 3’ 135’/135’
ALP150B 4” 3” 135’/135’
ALP210B 4” 3” 135’/135’
ALP285B 4” 4” 100’/100’
ALP399 4” 4” 100’/100’
NOTE:SnorkelsareapprovedforusewithPVCventing.Intake&ventlengthscombined.90°=5equivalent
feet.Terminalsdonotcounttowardsventfeetlength
FIELD ADAPTABLE KIT AVAILABLE FOR
WALL HUNG CONFIGURATION:
(forALP080throughALP210only)
Part#102991-01
1
Thermalefficiency
Alpine Dimensions (Inches)
Model A B C D E F G H J L M N O P Q
ALP080B 12-9/16 5-5/8 7-5/16 9-5/16 5-15/16 1/2 1 1 * 8 32-3/16 21-3/4 16-11/16 12-1/2 4-3/4
ALP105B 14 5-13/16 7-5/16 10-3/4 5-15/16 1/2 1 1 * 8 32-3/16 21-3/4 16-11/16 12-1/2 4-3/4
ALP150B 19-11/16 5-13/16 7-5/16 16-7/16 5-15/16 1/2 1 1 * 8 32-3/16 21-3/4 16-11/16 12-1/2 4-3/4
ALP210B 23-15/16 5-13/16 7-5/16 17-1/8 5-15/16 1/2 1 1 * 8 32-3/16 21-3/4 16-11/16 12-1/2 4-3/4
ALP285B 21-13/16 7-5/16 14-1/8 18 12-1/4 3/4 1-1/4 1-1/4 * 8-5/16 43-7/16 32-7/16 17-5/16 12-3/16 4-3/4
ALP399 28-7/8 6-3/16 13-1/16 23-3/4 15-13/16 1 1-1/2 1-1/2 * 8-5/16 43-7/16 32-7/16 17-5/16 12-3/16 4-3/4
NOTES:
DOEHeatingCapacity(ALP080throughALP285);GrossOutput(ALP399)
SafetyReliefValvePressure,Water(ALP080BthruALP285B)–30PSIstd.;
50PSI,80PSI,and100PSIoptional
SafetyReliefValvePressure,Water(ALP399only)-50PSIstd.;
80PSIand100PSIoptional
ASMEcertified160PSIMaximumAllowableWorkingPressureat210ºF.
Maxallowabletemperaturesetting210ºF
Targetsetpointis190°F,automaticresethighlimitsetpointis200°Fand
manualresethighlimitsetpointis210°F
Boilersshippedsetfornaturalgas;fieldadjustmentforLP(seeinstructionmanual)
Forelevationsabove2000feet,reduceratingsfourpercent(4%)
per1000feetabovesealevel
2
Grossoutput
3