Page #1 background image
Hybrid electronic mixing valve
6000 Series LEGIOMIX 2.0
1
CONTENTS
Product range
Characteristic components
Package content
Technical specifications
Operating principle
Application diagram
Regulator-actuator
Wiring diagrams
Electronic boards description
Cables pathway
Cables wiring and positioning
Probes connection
Recommended minimum distances
Front panel
Indication on LCD display
Operating status
Plumbing installation
Commissioning
Thermal disinfection
Maintenance
Functional faults
Seals
Troubleshooting
Regulator-actuator replacement/rotation
Thermostatic function
2
3
4
6
5
7
8
9
10
11
Application diagrams
12
INSTALLATION AND COMMISSIONING MANUAL
© Copyright 2017 Caleffi
H0002123
www.caleffi.com
Operating principle
The electronic hybrid mixing valve combines the typical function
of the mechanical thermostatic mixing valve and the management
efciency of an electronic mixing valve in a single device.
The thermostatic mixing valve uses the mechanical action
performed by the internal control thermostatic element, which
responds promptly to any variation in temperature, pressure and
inlet ow rate to quickly restore the mixed water temperature value
at the outlet.
This standard mixing valve is effectively handled by a motorised
actuator that, upon the signal coming from the temperature probes
and under the control of a specic regulator, changes the mixed
water temperature set position.
The electronic regulator, directly on the actuator, allows the
mixed water temperature control according to different functional
programs, both for normal control and for the thermal disinfection
for the prevention of Legionella.
An optional memory system allows recording every minute of ow
temperature, return temperature, alarm and functional statuses,
useful for monitoring the operating status of the entire system.
Appropriate relays are used to manage the alarms and external
appliances, for example for loading accumulation hot water and
switching on/off the recirculation pump.
The regulator is tted for remote control with specic transmission
protocols such as MODBUS, through optional board, for use in
Building Management Systems (BMS).
The device is provided with CE mark in accordance with
directives 2014/35/EU and 2014/30/EU.
2

Other manuals for CALEFFI 6000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the CALEFFI 6000 Series and is the answer not in the manual?

CALEFFI 6000 Series Specifications

General IconGeneral
BrandCALEFFI
Model6000 Series
CategoryControl Unit
LanguageEnglish

Related product manuals