EasyManua.ls Logo

Campbell MetSENS Series - Page 34

Campbell MetSENS Series
39 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5. Click the Terminal tab.
6. Select All Caps Mode.
7. Press Enter until the data logger responds with the data logger (CR1000X>) prompt.
8. Type SDI12 and press Enter.
9. At the Select SDI12 Port prompt, type the number corresponding to the control port where
the sensor is connected and press Enter. In this example the sensor is connected to C3. The
response Entering SDI12 Terminal indicates that the sensor is ready to accept SDI-12
commands.
10. To query the sensor for its current SDI-12 address, type ?! and press Enter. The sensor
responds with its SDI-12 address. If no characters are typed within 60 seconds, the mode is
exited. In that case, simply type SDI12 again, press Enter, and type the correct control port
number when prompted.
MetSENS-Series Compact Weather Sensors 31

Related product manuals