37
7)
Press the reset button on
the ignition control
within the alotted time
Master Boiler
8) Press
and
9) Press [Lead Lag Master Configuration]
10) Press [Advanced Settings >]
11) Press the to arrive at Outdoor Reset
12) Select Enable: Enabled
13) Select Maximum outdoor temperature (WWSD)
14) Select Minimum outdoor temperature (Outdoor Design)
15) Select Low Water Temperature (Min. Water Temp)
16) Select Outdoor boost maximum off point (Design Max.)
17) Press [Show Line] to confirm reset curve
18) Press the to arrive at Warm Weather Shutdown
19) Select Enable = Shutdown after demand ends