99-0053
Rev. 01
INSTALLATION OPERATION
AND SERVICE MANUAL
MICOFLAME SERIES 2
GAS FIRED COMMERCIAL COPPER TUBE BOILERS
FOR HYDRONIC HEATING
Models; MFH800, 1000, 1200, 1400, 1600, 1800, 2000
HOT WATER SUPPLY
Models; MFW800, 1000, 1200, 1400, 1600, 1800, 2000
WARNING: If the information in these instructions is not
followed exactly, a fire or explosion may result causing
property damage, personal injury or death
Do not store or use gasoline or other flammable
vapours and liquids in the vicinity of this or any other
appliance.
WHAT TO DO IF YOU SMELL GAS
o Do not try to light any appliance,
o Do not touch any electrical switch; do not use any
phone in your building,
o Immediately call your gas supplier from a
neighbour’s phone. Follow the gas supplier’s
instructions,
o If you cannot reach your gas supplier, call the fire
department.
Qualified installer, service agency or the gas supplier
must perform installation and service.
To the installer: After installation, these instructions must be
given to the end user or left on or near the heater.
To the End User: This booklet contains important information
about this heater. Retain for future reference.
CAMUS HYDRONICS LTD.
6226 Netherhart Road, Mississauga, Ontario, L5T 1B7

Questions and Answers

  • G
    Gary OnealAug 2, 2025
    What to do if pilot sparks but does not light on Camus Hydronics MICOFLAME 2?
    • D
      Donna MaldonadoAug 2, 2025
      If the pilot sparks but doesn't light in your Camus Hydronics Boiler, first ensure the main manual valve is open. Then, follow the lighting instructions to bleed any air from the pilot line. If the problem persists, remove the main burner and check for any moisture or dirt in the pilot or pilot line. Also, make sure the pilot is sealed to the main burner base and all gas connections are tight.
  • M
    Marvin ConleyAug 6, 2025
    Why does main burner light but cycles off after a few minutes on Camus Hydronics Boiler?
    • F
      Frank SmithAug 6, 2025
      If the main burner of your Camus Hydronics Boiler lights but cycles off after a few minutes, you should first check that the high limit is set high enough to prevent short cycling. Also, adjust the pilot pressure to ensure a steady flame. If the issue continues, remove the main burner and adjust the pilot shield, cleaning the ignition sensor.
  • M
    Michael RogersAug 10, 2025
    Why does pilot light momentarily, go out and then spark again repeatedly on Camus Hydronics MICOFLAME 2 Boiler?
    • K
      Kathy MercerAug 10, 2025
      If the pilot light on your Camus Hydronics Boiler lights momentarily, goes out, and then sparks repeatedly, start by observing the pilot for proper flame and adjust it if necessary. Next, check the pilot flame signal, ensuring it's properly set to generate 1.5 µA D.C. on average. Then, remove the main burner and make sure the igniter and ground electrodes are positioned correctly, cleaning them with steel wool if needed. Finally, verify that the back of the burner box is fully engaged into the retaining slot in the combustion chamber base.
  • M
    Michael WilsonAug 14, 2025
    How to fix a Camus Hydronics MICOFLAME 2 Boiler that starts to whine as the temperature rise increases?
    • K
      Kristin RossAug 15, 2025
      If your Camus Hydronics Boiler starts to whine as the temperature rises, first make sure all air is bled from the system. Then, check that the static pressure in the cold system is at least 15 psig. Also, check the temperature rise across the boiler to ensure adequate water flow. If necessary, increase the static water pressure and decrease the gas pressure.
  • S
    stefaniegloverAug 19, 2025
    What to do if pilot lights but main burner does not fire on Camus Hydronics MICOFLAME 2?
    • J
      Jeffrey PayneAug 19, 2025
      If the pilot light is on but the main burner does not fire on your Camus Hydronics Boiler, first ensure the high limit is set high enough to prevent short cycling. Then, check the pilot flame signal (µA). Adjust the pilot pressure for a steady flame. Finally, remove the main burner and check the position of the igniter and ground electrode, cleaning them with steel wool if necessary.
  • V
    vargasaustinAug 25, 2025
    How to troubleshoot power light not lit on Camus Hydronics MICOFLAME 2 Boiler?
    • M
      Mary CampbellAug 25, 2025
      If the power light is not lit when the switch is flipped to “ON” on your Camus Hydronics Boiler, check the wiring to the switch, the circuit breaker, and the fuse.
  • F
    franciscowattsAug 28, 2025
    What to do if water flow light remains off on Camus Hydronics MICOFLAME 2 Boiler?
    • L
      Lisa EstesAug 28, 2025
      If the water flow light remains off on your Camus Hydronics Boiler, verify that the pump is running and check the wiring to the flow switch.

Summary

INTRODUCTION

GENERAL INSTRUCTIONS

WARRANTY OVERVIEW

BOILER LOCATION

PROVIDE AIR FOR COMBUSTION AND VENTILATION

ELECTRICAL WIRING

STAGING OPERATION

GAS SUPPLY AND PIPING

VENTING

OUTDOOR VENTING

Procedures for venting the appliance outdoors.

SIDEWALL VENTING

Guidelines for venting through a building's side wall.

OUTDOOR AIR KIT

Instructions for using an outdoor air intake system.

FILTER KIT

Description of an optional filter for air intake.

STANDARD VENTING

Details for conventional venting installations.

VENTING FOR CONDENSING APPLICATION

Specific venting needs for high-efficiency models.

RELIEF VALVE

FREEZE PROTECTION

WARNING REGARDING CHILLED WATER SYSTEMS

PIPING OF SYSTEM TO BOILER

PLACING BOILER IN OPERATION

IGNITION SYSTEM SAFETY SHUT-OFF DEVICE

LOW WATER TEMPERATURE SYSTEMS

INSTANTANEOUS WATER HEATER

PILOT AND MAIN BURNER FLAMES

MAIN BURNER

Details on the primary burner's flame and combustion.

PILOT BURNER

Information on the pilot flame and ignition system.

OPERATION AND SERVICE

LIGHTING INSTRUCTIONS

TROUBLE SHOOTING GUIDE

TYPICAL GAS TRAIN

ELECTRICAL DIAGRAMS

EXPLODED VIEW

MICO FLAME REPLACEMENT PARTS LIST

WARRANTY

HEAT EXCHANGER WARRANTY

Specific warranty coverage for the heat exchanger.

BURNER WARRANTY

Warranty coverage for the burner components.

OTHER PART WARRANTY

Warranty terms for remaining appliance parts.