INSTALLATION OPERATION
AND SERVICE MANUAL
MODULATING MICOFLAME SERIES
GAS FIRED RESIDENTIAL AND COMMERCIAL COPPER TUBE
BOILERS
FOR HYDRONIC HEATING
Non-Condensing Models; MFH060, 100, 150, 200, 250, 300, 400, 500, 600
Condensing Models; MFH062, 102, 152, 202, 252, 302, 402, 502, 602
HOT WATER SUPPLY
Non-Condensing Models; MFW060, 100, 150, 200, 250, 300, 400, 500, 600
Condensing Models; MFW062, 102, 152, 202, 252, 302, 402, 502, 602
WARNING: If the information in these instructions is not
followed exactly, a fire or explosion may result causing
property damage, personal injury or death
Do not store or use gasoline or other flammable
vapours and liquids in the vicinity of this or any other
appliance.
WHAT TO DO IF YOU SMELL GAS
o Do not try to light any appliance,
o Do not touch any electrical switch; do not use any
phone in your building,
o Immediately call your gas supplier from a
neighbour’s phone. Follow the gas supplier’s
instructions,
o If you cannot reach your gas supplier, call the fire
department.
Qualified installer, service agency or the gas supplier
must perform installation and service.
To the installer: After installation, these instructions must be
given to the end user or left on or near the heater.
To the End User: This booklet contains important information
about this heater. Retain for future reference.
CAMUS HYDRONICS LTD.
6226 Netherhart Road, Mississauga, Ontario, L5T 1B7

Table of Contents

Questions and Answers

  • P
    Penny StarkAug 7, 2025
    What to do if the main burner lights but cycles off after a few minutes in my Camus Hydronics MFH060?
    • C
      Carla SmithAug 7, 2025
      If the main burner on your Camus Hydronics Boiler lights but cycles off after a few minutes, try the following: * Ensure that the high limit is set high enough to prevent short cycling. * Adjust the pilot pressure to ensure a steady flame. * Remove the main burner, adjust the pilot shield, and clean the ignition sensor.
  • L
    Lauren SmithAug 11, 2025
    What to do if the pilot sparks but does not light on my Camus Hydronics MFH060?
    • D
      daniel55Aug 11, 2025
      If the pilot sparks but does not light on your Camus Hydronics Boiler, here are a few things you can check: 1. Make sure the main manual valve is open. 2. Follow the lighting instructions to bleed air out of the pilot line. 3. Remove the main burner and inspect for any moisture or dirt in the pilot or pilot line. 4. Ensure that the pilot is properly sealed to the main burner base. 5. Verify that all gas connections are tight.
  • K
    Kaitlyn MasonAug 16, 2025
    Why does the pilot light on my Camus Hydronics MFH060 light momentarily, go out, and then spark again repeatedly?
    • N
      Natasha CookAug 16, 2025
      If the pilot light on your Camus Hydronics Boiler lights momentarily, goes out, and then sparks again repeatedly, consider these steps: * Observe the pilot for proper flame and adjust if necessary. * Check the pilot flame signal, ensuring it's properly set to generate 1.5 µA D.C. on average. * Remove the main burner and ensure that the igniter and ground electrodes are positioned correctly; clean them with steel wool if needed. * Verify that the back of the burner box is fully engaged into the retaining slot in the combustion chamber base.
  • M
    Melissa DunnAug 20, 2025
    What to do if the pilot light lights but the main burner does not fire on my Camus Hydronics MFH060 Boiler?
    • J
      Jared WilsonAug 20, 2025
      If the pilot light on your Camus Hydronics Boiler lights but the main burner does not fire, try these steps: * Make sure the high limit is set high enough to prevent short cycling. * Check the pilot flame signal (µA). * Adjust the pilot pressure for a steady flame. * Remove the main burner and check the position of the igniter and ground electrode. Clean with steel wool if necessary.
  • M
    Mary WhiteAug 25, 2025
    How to fix a Camus Hydronics Boiler that starts to whine as the temperature rise increases?
    • J
      Jaime ThompsonAug 25, 2025
      If your Camus Hydronics Boiler starts to whine as the temperature rises, try the following: * Make sure that all air is bled from the system. * Verify that the static pressure in the cold system is at least 15 psig. * Check the temperature rise across the boiler to ensure adequate water flow. * If necessary, increase the static water pressure and decrease the gas pressure.
  • K
    Kelsey LoweAug 28, 2025
    What to do if the water flow light remains off on my Camus Hydronics Boiler?
    • D
      Douglas HamiltonAug 28, 2025
      If the water flow light remains off on your Camus Hydronics Boiler, you can try: * Verifying that the pump is running. * Checking the wiring to the flow switch.
  • P
    Patrick CharlesSep 1, 2025
    How to troubleshoot a Camus Hydronics Boiler when the power light is not lit?
    • J
      Jillian HenrySep 1, 2025
      If the power light is not lit when the switch is flipped to “ON” on your Camus Hydronics Boiler, you should: * Check the wiring to the switch. * Check the circuit breaker. * Check the fuse.