EasyManua.ls Logo

Camus Hydronics MFH060 - Mode 3: Dedicated Domestic Hot Water Operation: Adjust Display

Camus Hydronics MFH060
66 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
33
18.5 MODE 3: DEDICATED DOMESTIC HOT WATER OPERATION: ADJUST DISPLAY
From the Home display;
1) Press simultaneously to view the following parameters:
Display
Parameter
Name
Parameter Description Parameter Range
Mode
Operating mode for the boiler.
NOTE: A complete description of
each mode can be found in
section 8.4 Modes of Operation in
this manual.
1 to 8
Default = 1
Boiler Target
Temperature
To provide a target setpoint for
the heating system. Setpoint is
controlled to the inlet sensor
OFF, 70 to 220
o
F
(OFF,21 to 104
o
C)
Default = 120
o
F
(82
o
C)
DHW Target
Temperature
To provide a target setpoint for
the DHW system. Setpoint is
controlled to the DHW sensor
OFF, 70 to 190
o
F
(OFF, 21 to 88
o
C)
Default = 140
o
F
(54
o
C)
DHW
Differential
To provide a modulation rate
above and below the DHW
Target Temperature. For
example, if the value is 10
o
F and
the DHW Target Temperature is
160
o
F the boiler will begin to
modulate at 155
o
F and shut off at
165
o
F.
2 to 10
o
F
(1 to 5
o
C)
Default = 3
o
F (1
o
C)
Differential
Temperature
To provide a modulation rate
above and below the Boiler
Target temperature. For example,
if the value is 10
o
F and the Boiler
Target is 160
o
F the boiler will
begin to modulate at 155
o
F and
shut off at 165
o
F.
Au, 2 to 42
o
F
(Au, -17 to 5
o
C)
Default = Au
Pump Delay
Boiler post pump time after
burner has shut off, in seconds.
OFF, 0:20 to 9:55
min, On
Default = 1:00 min
Temperature
Units
Select the desired unit of
measurement
o
F,
o
C
Default =
o
F

Table of Contents

Related product manuals