SmartLock
®
Controller Page 18 of 26
Installation Manual Nov 2018 • Rev. 3.2
Input Wiring
EXIT BUTTON, HANDICAP BUTTON, DOOR CONTACT
NOTE: DO NOT apply power or attempt to switch any current through
these inputs as this will result in damage to the controller.
NOTE: If not connecting a door contact, make sure you set switch position 8
to ON (right in orientation shown) to bypass/disable the door contact input.
Otherwise, the door will be in alarm condition.
NOTE: Exit Button requires momentary closure to activate relay. Door
Contact is used for forced-entry and door-held-open annunciation, and also
deactivates the lock relay when the door closes.
1 2 3 4 5 6 7 8
ON
EXIT BUTTON
- NORMALLY OPEN
- MOMENTARY TO
ACTIVATE
HANDICAP BUTTON
- NORMALLY OPEN
- MOMENTARY TO ACTIVATE
- ENABLED ONLY AFTER
VALID CARD OR
EXIT BUTTON
DOOR CONTACT
- NORMALLY CLOSE
EXIT
HC
DC
IF YOU ARE CONNECTING A DOOR CONTACT
SET DIP SWITCH 8 TO OFF (LEFT)
IF YOU ARE CONNECTING A DOOR CONTACT
SET DIP SWITCH 8 ON (RIGHT)
NOT
OFF