SmartLock
®
Controller Page 8 of 26
Installation Manual Nov 2018 • Rev. 3.2
SmartLock Controller Layout
Important Notes:
1. Each controller must have a unique address.
Refer to the Controller Address Table.
2. Exit reader must be Wiegand only. Native iButton
®
reader not supported
for exit.
3. Before connecting readers with power ON, make sure Reader Voltage
Selection Jumper is set to proper voltage for reader, otherwise the reader
may be damaged.
4. Do NOT connect power to any inputs on the controller.
5. The Door Contact Input should be bypassed, if not used, by using a
jumper wire across the input or setting the switch to ignore the input. Refer
to the Door Contact Bypass Switch Setting.
6. This controller utilizes “self-resetting” fuses. There are no field-serviceable
parts.
1 2 3 4 5 6 7 8
ON
WIEGAND
DATA LED
COMMS
LED
OFF
ON
8
1
+5V
+12V
N/O
N/C
N/O N/O
N/C N/C
+12 VDC
INPUT
EXIT READER
(WIEGAND)
ENTRY READER
(WIEGAND)
ENTRY READER
or
PROGRAMMING MODULE
(iBUTTON)
DOOR CONTACT
EXIT BUTTON
DOOR OPERATOR
(INPUTS)
LOCK CONTROL
DOOR OPERATOR
FORCED/HELD OPEN
(OUTPUTS)
RS-485
COMMUNICATIONS
RELAY LEDS
ADDRESS
SWITCH
READER VOLTAGE
SELECTOR
DEFAULT
(DO NOT CHANGE)
LOCK
FORCED
/ DHO
DOOR
OPER.
FIRMWARE CHIP