ERASE CONTROLLER MEMORY, DIAGNOSTICS
1. Disconnect communication and device wiring.
2. To erase controller memory (factory default), set all switches to the
OFF position (left on diagram above).
3. Disconnect power from the board momentarily then re-connect power.
4. The controller’s memory will be erased. All three relays will cycle
ON/OFF once the memory has been cleared. Relay outputs can be
verified during this stage.
NOTE: If the relays do not cycle ON/OFF, there may be a problem
with the unit.
5. Continue to set controller address and door contact bypass switch
settings.
SET CONTROLLER BAUD RATE
The default baud rate is 9600 bps with dip switch #7 set to on position.
SmartLock Pro, with firmware version 1.56 and up, also supports 38,400
bps. Follow the steps below to adjust the baud rate.
1. Set dip switch #7 to off position to enable 38,400 bps.
2. Ensure that the setting in the software is set to 38,400.
NOTE: Switch setting changes do not take effect until the power is
disconnected, then reconnected.