SmartLock
®
Controller Page 3 of 26
Installation Manual Nov 2018 • Rev. 3.2
CAUTION: EMERGENCY LOCKDOWN
Emergency lockdown functions must operate totally independent of the access
control system and must not rely on operation of card readers, access control panels,
communications networks, communications devices or host software. Cansec
accepts no responsibility for direct or consequential damages resulting from the
failure of emergency lockdown functions which are dependant in any way on the
operation of card readers, access control panels, communications networks,
communications devices or host software.
CA-PS123A Specifications Notice:
When using a pluggable 16 VAC standard 40 VA transformer:
Maximum Continuous Current (no battery attached): 2 amps for 12 VDC on
the Output.
Maximum Continuous Current (battery attached): 1.5 amps for 12 VDC on
the Output (battery will be charging when needed).
Using a wire in 16 VAC standard 75 VA transformer:
Maximum Continuous Current (no battery attached): 2.5 amps for 12 VDC
on the Output.
Maximum Continuous Current (battery attached): 2.0 amps for 12 VDC on
the Output (battery will be charging when needed).
Surge currents need to be taken into account. High current devices like
electric strikes and magnetic locks have surge currents which are usually
double the running current.
The CA-PS123A’s DC output is fused at 2.5 amps.
An electrician is not required for installation of this supply.