Mask index Par. Description Default UOM Min Max Possible value descr. R/W
Baa05 /P4 Select evaporation pressure probe position 5 0 15
0: --
1: U01…10: U10
11: SPV
12: MST
13: SL1
R/W
Select type of evaporation pressure probe 0 -- 0 3
0: RAT.0-5V
1: 4-20MA
2: 4-20MA REM
3: 4-20MA EXT
R/W
Evaporation pressure probe value 17.3 (250.0) barg/psig R
Maximum evaporation pressure probe value 0.0 (0.0) barg/psig min 200.0
(2938.0)
R/W
Minimum evaporation pressure probe value 0.0 (0.0) barg/psig -1.0 (-14.7) max R/W
Evaporation pressure probe off set 0.0 (0.0) bar/psi -10.0 (-146.9) 10.0 (146.9) R/W
Baa06 /P1 Select discharge temperature probe position 6 0 10
0: --
1: U01…10: U10
11: SPV
12: MST
13: SL1
R/W
Select type of discharge temperature probe 1 -- 0 5
0: CAREL NTC
1: CAREL NTC-HT
2: NTC SPKP**T0
3: TEMP.CUSTOM1
4: PT500
R/W
Discharge temperature reading °C (°F) R
Discharge temperature probe off set 0.0 (0.0) °C (°F) -50.0 (-90.0) 50.0 (90.0) R/W
Baa07 /P2 Select suction temperature probe position 4 0 10
0: --
1: U01…10: U10
11: SPV
12: MST
13: SL1
R/W
Select type of suction temperature probe 0 -- 0 5
0: NTC
1: NTC-HT
2: NTC SPKP**T0
3: 0-10V EXT.
4: TEMP.CUSTOM1
5: PT500
R/W
Suction temperature reading °C (°F) R
Suction temperature probe off set 0.0 (0.0) °C (°F) -50.0 (-90.0) 50.0 (90.0) R/W
Baa08 /Fq Select liquid temperature probe position 8 0 10
0: --
1: U01…10: U10
11: SPV
12: MST
13: SL1
R/W
Select type of liquid temperature probe 0 -- 0 2
0: NTC
1: NTC-HT
2: PT1000
R/W
Liquid temperature probe reading °C (°F) R
Liquid temperature probe off set 0.0 (0.0) °C (°F) -50.0 (-90.0) 50.0 (90.0) R/W
Baa09 /FI Select room temperature probe position 0 0 15
0: --
1: U01…10: U10
11: SPV
12: MST
13: SL1
R/W
Select type of room temperature probe 0 -- 0 2
0: NTC
1: NTC-HT
2: PT1000
R/W
Room temperature probe reading °C (°F) R
Room temperature probe off set 0.0 (0.0) °C (°F) -50.0 (-90.0) 50.0 (90.0) R/W
Baa10 /FL Select room humidity probe position 0 0 15
0: --
1: U01…10: U10
11: SPV
12: MST
13: SL1
R/W
Select type of room humidity probe 0 -- 0 2
0: 4-20MA
1: 0-1V
2: 0-10V
R/W
Room humidity probe reading %rH R
Maximum room humidity probe value 100.0 %rH min 100.0 R/W
Minimum room humidity probe value 0.0 %rH 0.0 max R/W
Room humidity probe off set 0.0 %rH -20.0 20.0 R/W
Baa11 /FM Select glass temperature probe position 0 0 15
0: --
1: U01…10: U10
11: SPV
12: MST
13: SL1
R/W
Select type of glass temperature probe 0 -- 0 2
0: NTC
1: NTC-HT
2: PT1000
R/W
Glass temperature probe reading °C (°F) R
Baa11 Glass temperature probe off set 0.0 (0.0) °C (°F) -50.0 (-90.0) 50.0 (90.0) R/W
Baa12 /FW Select water inlet temperature probe position 0 0 14
0: --
1: U01…10: U10
11: SPV
R/W
Select type of water inlet temperature probe 0 -- 0 2
0: NTC
1: NTC-HT
2: PT1000
R/W
Water inlet temperature probe reading °C (°F) R
Water inlet temperature probe off set 0.0 (0.0) °C (°F) -50.0 (-90.0) 50.0 (90.0) R/W
Baa13 /FY Select water outlet temperature probe position 0 0 14
0: --
1: U01…10: U10
11: SPV
R/W
Select type of water outlet temperature probe 0 -- 0 2
0: NTC
1: NTC-HT
2: PT1000
R/W
Water outlet temperature probe reading °C (°F) R
Water outlet temperature probe off set 0.0 (0.0) °C (°F) -50.0 (-90.0) 50.0 (90.0) R/W