Mask index Par. Description Default UOM Min Max Possible value descr. R/W
Baa14 /FG Select position of auxiliary probe 1 0 -- 0 15
0: --
1: U01…10: U10
11: SPV
12: MST
13: SL1
R/W
Select type of auxiliary probe 1 0 -- 0 16
0: NTC
1: PT1000
2: 0/1V
3: 0/10V
4: 4/20MA
5: 0/20MA
6: ON/OFF
?8: 0/5V RAT.
9: NTC HT
13: PTC
14: PT500
15: PT100
R/W
Baa14 Select function of auxiliary probe 1 0 -- 0 3
0: TEMPERATURE
1: PRESSURE
2: HUMIDITY
3: GENERIC
R/W
Auxiliary probe 1 °C (°F) /%rH/
barg
R
Minimum value of range for auxiliary probe 1 0.0 (32.0) °C (°F) /%rH/
barg
-999.9 max R/W
Maximum value of range for auxiliary probe 1 0.0 (32.0) °C (°F) /%rH/
barg
min 999.9 R/W
Auxiliary probe 1 off set 0.0 (0.0) °C (°F) /%rH/
barg
-999.9 999.9 R/W
Baa15 /FH Select position of auxiliary probe 2 0 -- 0 15
0: --
1: U01…10: U10
11: SPV
12: MST
13: SL1
R/W
Select type of auxiliary probe 2 0 -- 0 16
0: NTC
1: PT1000
2: 0/1V
3: 0/10V
4: 4/20MA
5: 0/20MA
6: ON/OFF
?8: 0/5V RAT.
9: NTC HT
13: PTC
14: PT500
15: PT100
R/W
Select function of auxiliary probe 2 0 -- 0 3
0: TEMPERATURE
1: PRESSURE
2: HUMIDITY
3: GENERIC
R/W
Auxiliary probe 2 °C (°F) /%rH/
barg
R
Minimum value of range for auxiliary probe 2 0.0 (32.0) °C (°F) /%rH/
barg
-999.9 max R/W
Maximum value of range for auxiliary probe 2 0.0 (32.0) °C (°F) /%rH/
barg
min 999.9 R/W
Auxiliary probe 2 off set 0.0 (0.0) °C (°F) /%rH/
barg
-999.9 999.9 R/W
Baa16 /FO Condenser air outlet temperature 0 0 14
0: --
1: U01…10: U10
11: SPV
R/W
Select type of condenser air outlet temperature 0 -- 0 2
0: NTC
1: NTC-HT
2: PT1000
R/W
Condenser air outlet temperature °C (°F) R
Condenser air outlet temperature probe off set 0.0 (0.0) °C (°F) -50.0 (-90.0) 50.0 (90.0) R/W
Baa17 /FE Select discharge temperature probe position comp 1 6 0 10
0: --
1: U01…10: U10
R/W
Select type of discharge temperature probe comp 1 1 -- 0 2
0: CAREL NTC
1: CAREL NTC-HT
2: PT1000
R/W
Discharge temperature reading comp 1 °C (°F) R
Discharge temperature probe off set comp 1 0.0 (0.0) °C (°F) -50.0 (-90.0) 50.0 (90.0) R/W
Baa18 /FF Select discharge temperature probe position comp 2 6 0 10
0: --
1: U01…10: U10
R/W
Select type of discharge temperature probe comp 2 1 -- 0 2
0: CAREL NTC
1: CAREL NTC-HT
2: PT1000
R/W
Discharge temperature reading comp 2 °C (°F) R
Discharge temperature probe off set comp 2 0.0 (0.0) °C (°F) -50.0 (-90.0) 50.0 (90.0) R/W
Baa19 /FN Select discharge temperature probe position comp 3 6 0 10
0: --
1: U01…10: U10
R/W
Select type of discharge temperature probe comp 3 1 -- 0 2
0: CAREL NTC
1: CAREL NTC-HT
2: PT1000
R/W
Discharge temperature reading comp 3 °C (°F) R
Discharge temperature probe off set comp 3 0.0 (0.0) °C (°F) -50.0 (-90.0) 50.0 (90.0) R/W
Baa20 /FP Select discharge temperature probe position comp 4 6 0 10
0: --
1: U01…10: U10
R/W
Select type of discharge temperature probe comp 4 1 -- 0 2
0: CAREL NTC
1: CAREL NTC-HT
2: PT1000
R/W
Discharge temperature reading comp 4 °C (°F) R
Discharge temperature probe off set comp 4 0.0 (0.0) °C (°F) -50.0 (-90.0) 50.0 (90.0) R/W