39
ENG
Heos +0300078EN - rel. 1.6 - 23.11.2017
Mask index Par. Description Default UOM Min Max Possible value descr. R/W
Baa21 /Fr Select discharge temperature probe position comp 5 6 0 10
0: --
1: U01…10: U10
R/W
Select type of discharge temperature probe comp 5 1 -- 0 2
0: CAREL NTC
1: CAREL NTC-HT
2: PT1000
R/W
Discharge temperature reading comp 5 °C (°F) R
Discharge temperature probe off set comp 5 0.0 (0.0) °C (°F) -50.0 (-90.0) 50.0 (90.0) R/W
Bab01 /LA Select modulating fan output position 0 -- 0 3
0: --; 1: Y1; 2: Y2; 3: Y3
R/W
Modulating fan output % reading 0 % 0 100 R
Analogue output voltage - V 0.0 10.0 R
Maximum voltage 10 V min 10.0 R/W
Minimum voltage 0 V 0.0 max R/W
Bab02 /Lb Select anti-sweat heater output position 0 -- 0 3
0: --; 1: Y1; 2: Y2; 3: Y3
R/W
Anti-sweat heater output % reading 0 % 0 100 R
Analogue output voltage - V 0.0 10.0 R
Maximum voltage 10 V min 10.0 R/W
Minimum voltage 0 V 0.0 max R/W
Bab05 /LE Select auxiliary output position 0 -- 0 3
0: --; 1: Y1; 2: Y2; 3: Y3
R/W
Auxiliary output % reading 0 % 0 100 R
Analogue output voltage - V 0.0 10.0 R
Maximum voltage 10 V min 10.0 R/W
Minimum voltage 0 V 0.0 max R/W
Bab06 /LF Select water-cooled condenser output position 0 -- 0 3
0: --; 1: Y1; 2: Y2; 3: Y3
R/W
Water-cooled condenser output % reading 0 % 0 100 R
Analogue output voltage - V 0.0 10.0 R
Maximum voltage 10 V min 10.0 R/W
Minimum voltage 0 V 0.0 max R/W
Bab07 /LG Select air-cooled condenser output position 0 -- 0 3
0: --; 1: Y1; 2: Y2; 3: Y3
R/W
Air-cooled condenser output % reading 0 % 0 100 R
Analogue output voltage - V 0.0 10.0 R
Maximum voltage 10 V min 10.0 R/W
Minimum voltage 0 V 0.0 max R/W
Bac01 /b1 Select remote alarm input position 0 -- 0 MaxPosDin
0: --
1: DI1, ..., 4: DI4
5: MST
R/W
Remote alarm input status 0 -- 0 1
0: CLOSED
1: OPEN
R
Select remote alarm input logic 0 -- 0 1
0: N.C.; 1: N.A.
R/W
Remote alarm input function 0 -- 0 1
0: NOT ACTIVE
1: ACTIVE
R
Bac02 /b2 Select delayed remote alarm input position 0 -- 0 5
0: --
1: DI1, ..., 4: DI4
5: MST
R/W
Delayed remote alarm input status 0 -- 0 1
0: CLOSED
1: OPEN
R
Select delayed remote alarm input logic 0 -- 0 1
0: N.C.; 1: N.A.
R/W
Delayed remote alarm input function 0 -- 0 1
0: NOT ACTIVE
1: ACTIVE
R
Bac03 /b3 Select enable defrost input position 0 -- 0 5
0: --
1: DI1, ..., 4: DI4
5: MST
R/W
Enable defrost input status 0 -- 0 1
0: CLOSED
1: OPEN
R
Select enable defrost input logic 0 -- 0 1
0: N.C.; 1: N.A.
R/W
Enable defrost input function 0 -- 0 1
0: NOT ACTIVE
1: ACTIVE
R
Bac04 /b4 Select start network defrost input position 0 -- 0 5
0: --
1: DI1, ..., 4: DI4
5: MST
R/W
Start network defrost input status 0 -- 0 1
0: CLOSED
1: OPEN
R
Select start network defrost input logic 0 -- 0 1
0: N.C.; 1: N.A.
R/W
Start network defrost input function 0 -- 0 1
0: NOT ACTIVE
1: ACTIVE
R
Bac05 /b5 Select door sensor input position 0 -- 0 5
0: --
1: DI1, ..., 4: DI4
5: MST
R/W
Door sensor input status 0 -- 0 1
0: CLOSED
1: OPEN
R
Select door sensor input logic 0 -- 0 1
0: N.C.; 1: N.A.
R/W
Door sensor input function 0 -- 0 1
0: NOT ACTIVE
1: ACTIVE
R
Bac06 /b6 Select remote on/off input position 0 -- 0 5
0: --
1: DI1, ..., 4: DI4
5: MST
R/W
Remote on/off input status 0 -- 0 1
0: CLOSED
1: OPEN
R
Select remote on/off input logic 0 -- 0 1
0: N.C.; 1: N.A.
R/W
Remote on/off input function 0 -- 0 1
0: NOT ACTIVE
1: ACTIVE
R
Bac07 /b7 Select Day/Night input position 0 -- 0 5
0: --
1: ID1, ..., 4: ID4
5: U01, ..., 14: U10
R/W
Day/Night input status 0 -- 0 1
0: CLOSED
1: OPEN
R
Select Day/Night input logic 0 -- 0 1
0: N.C.; 1: N.A.
R/W
Day/Night input function 0 -- 0 1
0: NOT ACTIVE
1: ACTIVE
R
Bac09 /b9 Select curtain contact output position 0 -- 0 5
0: --
1: DI1, ..., 4: DI4
5: MST
R/W
Curtain contact output status 0 -- 0 1
0: CLOSED
1: OPEN
R
Select curtain contact output logic 0 -- 0 1
0: N.C.; 1: N.A.
R/W
Curtain contact output function 0 -- 0 1
0: NOT ACTIVE
1: ACTIVE
R