41
ENG
Heos +0300078EN - rel. 1.6 - 23.11.2017
Mask index Par. Description Default UOM Min Max Possible value descr. R/W
Bad03 /EC Select light output position 7 -- 0 8
0: --
1: DO1, ..., 8: DO8
9: Y1
10: Y2
11: Y3
R/W
Light output status 0 -- 0 1
0: OPEN
1: CLOSED
R
Select light output logic 0 -- 0 1
0: N.A; 1: N.C.
R/W
Light output function 0 -- 0 1
0: NOT ACTIVE
1: ACTIVE
W
Bad04 /Ed Select defrost output position 8 -- 0 8
0: --
1: DO1, ..., 8: DO8
9: Y1
10: Y2
11: Y3
R/W
Defrost output status 0 -- 0 1
0: OPEN
1: CLOSED
R
Select defrost output logic 0 -- 0 1
0: N.A; 1: N.C.
R/W
Defrost output function 0 -- 0 1
0: NOT ACTIVE
1: ACTIVE
W
Bad05 /EE Select alarm output position 1 -- 0 8
0: --
1: DO1, ..., 8: DO8
9: Y1
10: Y2
11: Y3
R/W
Alarm output status 0 -- 0 1
0: OPEN
1: CLOSED
R
Select alarm output logic 0 -- 0 1
0: N.A; 1: N.C.
R/W
Alarm output function 0 -- 0 1
0: NOT ACTIVE
1: ACTIVE
W
Bad06 /EF Select auxiliary output position 0 -- 0 8
0: --
1: DO1, ..., 8: DO8
9: Y1
10: Y2
11: Y3
R/W
Auxiliary output status 0 -- 0 1
0: OPEN
1: CLOSED
R
Select auxiliary output logic 0 -- 0 1
0: N.A; 1: N.C.
R/W
Auxiliary output function 0 -- 0 1
0: NOT ACTIVE
1: ACTIVE
W
Bad07 /EG Select anti-sweat heater output position 0 -- 0 3
0: --
1: --
2: DO2
3: DO3
R/W
Anti-sweat heater output status 0 -- 0 1
0: OPEN
1: CLOSED
R
Select anti-sweat heater output logic 0 -- 0 1
0: N.A; 1: N.C.
R/W
Anti-sweat heater output function 0 -- 0 1
0: NOT ACTIVE
1: ACTIVE
W
Bad08 /EM Select liquid injection solenoid output position 0 -- 0 8
0: --
1: DO1, ..., 8: DO8
9: Y1
10: Y2
11: Y3
R/W
Liquid injection solenoid output status 0 -- 0 1
0: CLOSED
1: OPEN
R
Select liquid injection solenoid output logic 0 -- 0 1
0: N.A; 1: N.C.
R/W
Liquid injection solenoid output function 0 -- 0 1
0: NOT ACTIVE
1: ACTIVE
W
Bad09 /EN Select curtain contact output position 0 -- 0 8
0: --
1: DO1, ..., 8: DO8
9: Y1
10: Y2
11: Y3
R/W
Curtain contact output status 0 -- 0 1
0: CLOSED
1: OPEN
R
Select curtain contact output logic 0 -- 0 1
0: N.A; 1: N.C.
R/W
Curtain contact output function 0 -- 0 1
0: NOT ACTIVE
1: ACTIVE
W
Bad10 /Eo Select position of ON/OFF compressor output 0 -- 0 8
0: --
1: DO1, ..., 8: DO8
9: Y1
10: Y2
11: Y3
R/W
Status of ON/OFF compressor output 0 -- 0 1
0: CLOSED
1: OPEN
R
Select logic of ON/OFF compressor output 0 -- 0 1
0: N.A; 1: N.C.
R/W
ON/OFF compressor output function 0 -- 0 1
0: NOT ACTIVE
1: ACTIVE
W
Bad13 /Er
Select inverter valve output position 0 -- 0 8
0: --
1: DO1, ..., 8: DO8
9: Y1
10: Y2
11: Y3
R/W
Inverter valve output status 0 -- 0 1
0: OPEN
1: CLOSED
R
Select inverter valve output logic 0 -- 0 1
0: N.O. 1: N.C.
R/W
Inverter valve output function output 0 -- 0 1
0: NOT ACTIVE
1: ACTIVE
W
Bad14 /ES
Select condenser fan output position 0 -- 0 8
0: --
1: DO1, ..., 8: DO8
9: Y1
10: Y2
11: Y3
R/W
Condenser fan output status 0 -- 0 1
0: OPEN
1: CLOSED
R
Select condenser fan output logic 0 -- 0 1
0: N.O. 1: N.C.
R/W
Condenser fan output function 0 -- 0 1
0: NOT ACTIVE
1: ACTIVE
W