Mask index Par. Description Default UOM Min Max Possible value descr. R/W
Dca02 dt1 End defrost temperature 8.0 (46.4) °C (°F) -50.0 (-58.0) 50.0 (122.0) R/W
dP1 Maximum defrost duration 40 min 1 240 R/W
dd Dripping time after defrost (fans off ) 120 s 0 600 R/W
d9 Disable evaporation pressure alarm in defrost 0 -- 0 1
0: NO; 1: YES
R/W
Dca03 dI Interval between two consecutive defrosts 0=disabled 8 h 0 500 R/W
d4 Enable defrost at start-up 0 -- 0 1
0: NO; 1: YES
R/W
d5 Defrost delay at start-up or from digital input 0 min 0 240 R/W
Dca04 r3 Enable end defrost signal for maximum time 0 -- 0 1
0: NO; 1: YES
R/W
d2 Defrost control in pLAN 1 -- 0 2
0: START ONLY
1: START & END
2: LOCAL ONLY
R/W
d8 High temperature alarm bypass time after defrost and/or
door open
30 min 0 240 R/W
Dca05 d13 Restart control delay during maintenance 0=disabled 0 min 0 240 R/W
dR1 Enable compressor OFF in defrost 0 -- 0 1
0: NO; 1: YES
R/W
/10 Select probe used for end defrost (d0=4) 2 -- 0 3
0: CONTROL PROBE
1: OUTLET PROBE
2: DEFROST PROBE
3: INTAKE PROBE
R/W
Dca06 dG2 Compressor speed (defrost by reversing cycle) 50.0 rps cIc cIb R/W
dG3 Maximum acceleration in defrost by reversing cycle 1.0 rps cId cIE R/W
dG4 Out of envelope alarm delay (defrost by reversing cycle) 600 s 0 999 R/W
Dca07 dG5 4-way valve changeover delay in Defrost 10 s 0 99 R/W
dG6 4-way valve changeover delay after defrost 10 s 0 99 R/W
dG7 End defrost delay (defrost by reversing cycle) 60 s 0 180 R/W
Dca08 dG8 EXV mode at start defrost 1 -- 0 1
0: REG; 1: MAN
R/W
Manual EXV opening at start defrost 50 % 0 100 R/W
dG9 EXV mode during defrost 1 -- 0 1
0: REG; 1: MAN
R/W
Manual EXV opening during defrost 50 % 0 100 R/W
dG10 EXV mode at end defrost 1 -- 0 1
0: REG; 1: MAN
R/W
Manual EXV opening at end defrost 50 % 0 100 R/W
Dca09 dH2 Compressor speed (hot gas defrost) 80.0 % cIc cIb R/W
dH4 Out of envelope alarm delay (hot gas defrost) 600 s 0 999 R/W
Dca10 dH5 Bypass valve opening delay (hot gas defrost) 10 s 0 99 R/W
dH6 Bypass valve closing delay (hot gas defrost) 10 s 0 99 R/W
Dca11 dH7 Enable manual (hot gas defrost) 0 - 0 1
0: NO; 1: YES
R/W
dH8 Manual positioning (hot gas defrost) 0 % 0 100 R/W
Dca12 dH9 Defrost duration threshold (hot gas defrost) -2.0 (28.4) °C (°F) -5.0 (-23.0) 10.0 (50.0) R/W
dH10 Alarm delay after defrost (hot gas defrost) 2 min 0 99 R/W
Dcb01…4 td1…8 Scheduled defrost day 0 -- 0 11
0: NONE
1: MON
2: TUE
3: WED
4: THU
5: FRI
6: SAT
7: SUN
8: MON-FRI
9: MON-SAT
10: WEEKEND
11: ALWAYS
R/W
tt1…8 Scheduled defrost hours 0 -- 0 23 R/W
tt1…8 Scheduled defrost minutes 0 -- 0 59 R/W
tP1…8 Enable Power Defrost 0 -- 0 1
0: NO; 1: YES
R/W
Dcc01 d7 Enable skip defrost 0 -- 0 1
0: NO; 1: YES
R/W
dn Nominal defrost duration for skip defrost 45 min 0 240 R/W
do Number of defrosts to be performed when starting before
activating skip def.
7-- 1 9 R
Dcc02 dA1 Probe used for Running Time 0 -- 0 1
0: DEFROST
1: TEMP.SAT.EVAP.
R/W
d11 Running Time temperature set point -4.0 (24.8) °C (°F) -50.0 (-58.0) 30.0 (86.0) R/W
d10 Defrost duration in Running Time mode 0 min 0 240
0 = DISABLED
R/W
dA2 Delay at start-up before activating Running Time 120 min 0 480 R
Dcc03 ddt Additional temperature for power defrost 0.0 (0.0) °C (°F) -20.0 (-36.0) 20.0 (36.0) R/W
ddP Additional defrost duration in power defrost 0 min 0 60 R/W
Dcc04 dS0 Enable Sequential Stops 0 -- 0 1
0: NO; 1: YES
R/W
dS1 Compressor ON time for Sequential Stop defrost 180 min 0 999 R/W
dS2 Compressor OFF time for sequential Stop defrost 10 min 0 999 R/W
Dd01 F0 Confi gure fan management 0 -- 0 2
0: ALWAYS ON
1: BY SD -SV DIFFERENCE
2: BY. DEFROST TEMP.
R/W
F1 Fan activation threshold -5.0 (23.0) °C (°F) -50.0 (-58.0) 50.0 (122.0) R/W
F2 Enable fans off with controller off (OFF) 0 -- 0 1
0: NO; 1: YES
R/W
Dd02 F3 Enable fans off during defrost 0 -- 0 2
0: ALWAYS ON
1: ALWAYS OFF
2: ALWAYS ON, OFF IN dd
R/W
Fd Fan off time in post-dripping 60 s 0 240 R/W
Frd Fan diff erential 2.0 (3.6) °C (°F) 0.1 (0.2) 20.0 (36.0) R/W
Dd03 F6 Maximum fan speed 80 % min 100 R/W
F7 Minimum fan speed 10 % 0 max R/W
Dd04 F5 Fan cut-off temperatures 0.0 (32.0) °C (°F) -50.0 (-58.0) 50.0 (122.0) R/W
F8 Fan peak time 10 s 0 240 R/W
F9 Override fan output to 100% every: 0 min 0 240 R/W
Dd05 F10 OFF time during curtain closing 50 s 0 999 R/W
F11 OFF time during curtain opening 50 s 0 999 R/W
De01 rHo Anti-sweat modulation off set from dew point 2.0 (3.6) °C (°F) -20.0 (-36.0) 20.0 (36.0) R
rHd Anti-sweat heater diff erential modulation 0.0 (0.0) °C (°F) 0.0 (0.0) 20.0 (36.0) R/W
De02 rHB Anti-sweat modulation cut-off 10.0 (18.0) °C (°F) 0.0 (0.0) 20.0 (36.0) R/W
rHC Anti-sweat heater modulation cut-off diff erential 1.0 (1.8) °C (°F) 0.0 (0.0) 10.0 (18.0) R/W
De03 rHt Anti-sweat heater activation period 30 min 10 180 R/W
rHu Manual activation anti-sweat heaters percentage 70 % 0 100 R/W
De04 rH6 Minimum anti-sweat heater output 10 % 0 max R
rH7 Maximum anti-sweat heater output 100 % min 100 R/W