47
ENG
Heos +0300078EN - rel. 1.6 - 23.11.2017
Mask index Par. Description Default UOM Min Max Possible value descr. R/W
De05 rH8 Type of anti-sweat heater modulation 0 -- 0 1
0: P; 1: P+I
R/W
rH9 Anti-sweat heater integral time 60 s 0 999 R/W
De06 Ga Coeffi cient a” for glass temperature formula 2.0 (3.6) °C (°F) -20.0 (-36.0) 20.0 (36.0) R/W
Gb Coeffi cient b” for glass temperature formula 22 % 0 100 R/W
De07 Gc Coeffi cient c” for glass temperature formula 80 % 0 100 R/W
Df01 bA1 Showcase/cold room cleaning duration 240 min 0 360 R/W
Df02 bA3 Showcase cleaning with end via DI 0 -- 0 1
0: YES
1: NO
R/W
Df03 bA4 Enable dual temperature 0 0 1
0: NO ; 1:YES
R/W
bA5 Enable digital input 0 0 1
0: NO ; 1:YES
R/W
bA6 EPR activated by DO 0 0 1
0: set A ; 1:set B
R/W
Df04 bA7 Change status 0 0 1
0: set A ; 1:set B
R/W
St User temperature set point 2.0 (35.6) °C (°F) r1 r2 R/W
Df05/14 d0 Type of defrost/end defrost 0 0 6
0: ELECTR./ TEMP-TIMEOUT
1: REV. CYCLE/TEMP-TIME-
OUT
2: ELECTR./ TIMEOUT ONLY
3: REV. CYCLE/TIMEOUT ONLY
4: ELECTRIC/TIMEOUT +
TEMP. CONTROL
5: HOT GAS BYPASS/ TEMP-TI-
MEOUT
6: HOT GAS BYPASS/ TIME-
OUT ONLY
R/W
dt1 End defrost temperature 8.0 (46.4) °C (°F) -50.0 (-58.0) 50.0 (122.0) R/W
dP1 Maximum defrost duration 40 min 1 240 R/W
Df06/15 dI Interval between two consecutive defrosts 8 h 0 500 R/W
d2 Defrost control in pLAN 1 0 2
0: START ONLY
1: START AND END
2: LOCAL ONLY
R/W
/10 Select probe used for end defrost 2 0 3
1: OUTLET PROBE
2: DEFROST PROBE
3: INTAKE PROBE
R/W
Df07…10
Df16…19
td1…8 Scheduled defrost day 0 0 11
1: MON
2: TUE
3: WED
4: THU
5: FRI
6: SAT
7: SUN
8: MON-FRI
9: MON-SAT
10: WEEKEND
11: ALWAYS
R/W
tt1…8 Scheduled defrost hours 0 0 23 R/W
tt1…8 Scheduled defrost minutes 0 0 59 R/W
Df11/20 d11 Temperature set point for running time -4.0 (24.8) °C (°F) -50.0 (-58.0) 30.0 (86.0) R/W
d10 Defrost time for running time 0 min 0 240
0 = DISABLED
R/W
dA2 Delay at start-up to start Running time 120 min 0 480 R/W
Df12/21 F1 Fan activation threshold -5.0 (23.0) °C (°F) -50.0 (-58.0) 50.0 (122.0) R/W
F3 Enable fans off during defrost 0 0 2
0: ALWAYS ON
1: ALWAYS OFF
2: ALWAYS ON, OFF IN dd
R/W
Df13/22 AH High temperature alarm threshold Al.1 10.0 (50.0) °C (°F) -50.0 (-58.0) 50.0 (122.0)
if A1= 1: ABSOLUTE
R/W
10.0 (18.0) °C (°F) 0.0 (0.0) 50.0 (90.0)
if A1= 0: RELATIVE
R/W
AL Low temperature alarm threshold Al.1 4.0 (39.2) °C (°F) -50.0 (-58.0) 50.0 (122.0)
if A1= 1: ABSOLUTE
R/W
4.0 (7.2) °C (°F) 0.0 (0.0) 50.0 (90.0)
if A1= 0: RELATIVE
R/W
AH2 High temperature alarm threshold Al.2 10.0 (50.0) °C (°F) -50.0 (-58.0) 50.0 (122.0)
if A1= 1: ABSOLUTE
R/W
10.0 (18.0) °C (°F) 0.0 (0.0) 50.0 (90.0)
if A1= 0: RELATIVE
R/W
AL2 Low temperature alarm threshold Al.2 4.0 (39.2) °C (°F) -50.0 (-58.0) 50.0 (122.0)
if A1= 1: ABSOLUTE
R/W
4.0 (7.2) °C (°F) 0.0 (0.0) 50.0 (90.0)
if A1= 0: RELATIVE
R/W
PE2 Evaporator capacity 500 W 0 15000 R/W
Ea01 H0 Serial address for supervisor (BMS) 194 -- 0 199 R/W
H6 BMS communication speed 4 -- 0 4
0: 1200 BAUD
1: 2400 BAUD
2: 4800 BAUD
3: 9600 BAUD
4: 19200 BAUD
R
H7 BMS communication protocol 0 -- 0 2
0: CAREL
1: MODBUS
2: WINLOAD
3: MODEM GSM
4: RS232
R
Ea02 Modbus master protocol baud rate 4 -- 0 4
0: 1200
1: 2400
2: 4800
3: 9600
4: 19200
R/W
Modbus master protocol Stop bits 1 -- 0 1
0: 1; 1: 2
R/W
Modbus master protocol parity 0 -- 0 2
0: NO
1: EVEN
2: ODD
R/W
Timeout 500 ms 100 5000
Ea03 Master/Slave unit address 1 -- 1 6
1: MASTER
2: SLAVE 1...6: SLAVE 5
R/W
Eb01 Multi-evaporator unit with single compressor 0 0 1
0: NO; 1: YES
R/W
Eb02 Sn Number of slaves 0 -- 0 5 R/W
Eb03 PE1 Number of evaporators (for multi-evaporator) 1 -- 1 6 R/W
PES Enable modulating superheat 0 -- 0 1
0: NO; 1: YES
W
Eb04 PE2 Evaporator capacity 500 W 0 15000 R/W
Eb05 PE5 Multi-evaporator superheat control proportional gain 4.0 -- 1.0 99.9 R/W
PE6 Multi-evaporator superheat control integral time 120 s 0 999 R/W
PE7 Multi-evaporator superheat control off set 20.0 (36.0) °C (°F) 0.0 (0.0) 40.0 (72.0) R/W
Eb06 PEA Change unit delay in SuperHeat mode 180 s 0 999 R/W
PEB Modulating SuperHeat mode 0 -- 0 1
0: BEST UNIT; 1: ALL
R/W
Eb07 PEV Valve opening during oil recovery 80 % 0 100 R/W

Related product manuals